3-28
Programming and Parameters
167
Motor Ctrl Ackn
Displays the Motor Control Processor's acknowledgment to the Velocity Processor for the Motor Control Command bits.
169
SrLss ZeroSpdLim
Functionally equivalent to Par 160 [Zero Speed Lim], but is used exclusively in
Sensorless speed mode. The value is automatically set from Par 3 [Motor NP Hertz], Par
4 [Motor NP RPM] or Par 7 [Motor Poles]. The automatic setting corresponds to the rated
slip speed of the motor (synchronous speed - nameplate speed). The value can be
manually set.
Units:
Default:
Min/Max:
RPM
49.9975
0.0000/875.0000
✓ Real
171
Set Speed Lim
Creates a tolerance - hysteresis band around the value in Par 41 [Limited Spd Ref] for
comparison to average speed feedback. The comparison controls bit 14 [At Setpt Spd] of
Par 155 [Logic Status]. In general bit 14 [At Setpt Spd] turns on when the feedback is
within the tolerance of the reference. Technically - Turn-on level for rising feedback = Par
41 [Limited Spd Ref] - Limit. Turn-off level for rising feedback = {Limited Spd Ref} +
2(Limit). Turn-on level for falling feedback = [Limited Spd Ref} + Limit. Turn-off level for
falling feedback = [Limited Spd Ref] - 2(Limit).
Units:
Default:
Min/Max:
Comm Scale:
RPM
17.6400
0.0000/882.0000
Par 4 [Motor NP RPM] = 1.0
✓ ✓ Real
172
Setpt 1 Data
Provides data for comparison to Par 173 [Setpt1 TripPoint], driving bit 16 [At Setpt 1] of
Par 155 [Logic Status]. For more information, please see
.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
✓ ✓ Real
173
Setpt1 TripPoint
Provides the midpoint for operation of bit 16 [At Setpt 1] of Par 155 [Logic Status].
Units:
Default:
Min/Max:
P.U.
0.1000
-/+8.0000
✓ ✓ Real
174
Setpt 1 Limit
Creates a tolerance - hysteresis band around the value in Par 173 [Setpt1 TripPoint].
Turn-on level for ascending data = [Setpt1 TripPoint] - [Setpt 1 Limit]. Turn-off level for
ascending data = [Setpt1 TripPoint] + 2(Limit). Turn-on level for descending data =
[Setpt1 TripPoint] + Limit. Turn-off level for descending data = [Setpt1 TripPoint] - 2(Limit).
Units:
Default:
Min/Max::
P.U.
0.0100
0.0000/0.5000
✓ ✓ Real
175
Setpt 2 Data
Provides data for comparison to Par 177 [Setpt2 Limit], driving bit 17 [Above Setpt 2] of
Par 155 [Logic Status]. For more information, please see
.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
✓ ✓ Real
176
Setpt2 TripPoint
Provides the midpoint for operation of bit 16 [At Setpt 1] of Par 155 [Logic Status].
Units:
Default:
Min/Max:
P.U.
0.2000
-/+8.0000
✓ ✓ Real
177
Setpt 2 Limit
Creates a tolerance - hysteresis band around the value in Par 176 [Setpt2 TripPoint]. For
positive setpoints: Turn-on level = [Setpt2 TripPoint], Turn-off level = [Setpt2 TripPoint] -
Limit. For negative setpoints: Turn-on level = [Setpt2 TripPoint], Turn-off level = [Setpt2
TripPoint] + Limit.
Units:
Default:
Min/Max:
P.U.
0.0100
0.0000/0.5000
✓ ✓ Real
180
PI Output
The final output of the Process Control regulator. A value of 1 can represent either base
motor speed, motor rated torque, or 100% for some external function.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
Real
181
PI Reference
The reference input for the process control regulator. A value of 1 can represent either
base motor speed, motor rated torque, or 100% for some external function.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
✓ ✓ Real
182
PI Feedback
The feedback input for the process control regulator. A value of 1 can represent either
base motor speed, motor rated torque, or 100% for some external function.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
✓ ✓ Real
183
PI Command
Set bits to configure the process control regulator - enable or disable the regulator, enable or disable the time function generator and limit generator.
184
PI Lpass Filt BW
Sets the bandwidth of a single pole filter applied to the error input of the Process Control
regulator. The input to the filter is the difference between Par 181 [PI Reference] and Par
182 [PI Feedback]. The output of this filter is used as the input to the process control
regulator.
Units:
Default:
Min/Max:
R/S
0.0000
0.0000/500.0000
✓ ✓ Real
185
PI Preload
Presets the integrator of the Process Control regulator.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
✓ ✓ Real
No.
Name
Description
Values
Li
nkab
le
Read
-Wr
it
e
Da
ta
T
ype
Options
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Fault
Re
set
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Re
ser
ved
Po
w
er
D
ia
g
Pr
ec
har
ge
To
rq
ue Run
Fl
ux
Ru
n
CP
Ena
ble
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True
Options
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Time Lim
En
Enab
le
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True