Page 101

Programming and Parameters
3-47
356
Mtr Current Lim
Sets the largest allowable motor stator current. The online maximum value of this
parameter is Par 2 [Motor NP FLA]. The online minimum value is 105% of the current
indicated in Par 488 [Flux Current].
Units:
Default:
Min/Max:
P.U.
1.5000
0.0000/24.0000
✓ ✓ Real
358
Iq Ref Limited
Sets the limit value for the motor torque producing current.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
Real
359
Motor Flux Est
Q-axis motor voltage is divided by the motor frequency while field weakening is active.
This is used to convert the torque command to a motor current (Iqs) command.
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
Real
360
Min Flux
Sets the smallest level of flux used to convert Par 303 [Motor Torque Ref] to a current
reference above base speed.
Units:
Default:
Min/Max:
P.U.
0.2500
0.2500/1.0000
✓ ✓ Real
361
Flx LpassFilt BW
Sets the bandwidth of the filter that adjusts the response of the flux estimate used in the
torque to current conversion. Since the field time constant varies between motors, a
better control response may be obtained by adjusting the filter time constant. Normally
this parameter is not changed unless a significant disturbance occurs as the motor enters
field weakening AND Par 360 [Min Flux] is less than 1 per unit.
Units:
Default:
Min/Max:
R/S
12.0000
0.5000/100.0000
✓ ✓ Real
363
Curr Ref TP Sel
Enter or write a value to select current reference data displayed in Par 364 [Curr Ref TP
Data].
Default:
Options:
0
0
1
2
3
4
5
6
7
8
9
“Zero”
“Zero”
10 “Min Lim Stat”
“Iq Sum”
11 “Iq Prescale”
“Iq Lim In”
12 “IqtoIs Stat”
“Iq Lim Out”
13 ‘Flux Status”
“Iq Rate Stat”
14 “Flux LPF Out”
“Limited Flux”
15 “Is Per Unit”
“MtrCrLimStat”
16 “InPos IqLim”
“Lim'dMtrCrLm” 17 “InNeg IqLim”
“Iq Act Limit”
18 “Flx Filt Hld”
“Iq Cal Gain”
364
Curr Ref TP Data
Displays the data selected by Par 363 [Curr Ref TP Sel].
Units:
Default:
Min/Max:
P.U.
0.0000
-/+8.0000
Real
365
Encdr0 Loss Cnfg
Enter a value to configure the drive's response to an Encoder 0 Loss exception event.
• 0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
• 2 “FltCoastStop” - configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
Default:
Options:
2
0
1
2
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
366
Encdr1 Loss Cnfg
Enter a value to configure the drive's response to an Encoder 1 Loss exception event.
• 0 “Ignore” Configures the drive to continue running, as normal, when this event occurs
• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
Default:
Options:
0
0
1
2
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
367
FB Opt0 LossCnfg
Enter a value to configure the drive's response to a Feedback Option 0 Loss exception
event.
• 0 “Ignore” Configures the drive to continue running, as normal, when this event occurs
• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
Default:
Options:
0
0
1
2
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
368
FB Opt1 LossCnfg
Enter a value to configure the drive's response to a Feedback Option 1 Loss exception
event.
• 0 “Ignore” Configures the drive to continue running, as normal, when this event occurs
• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
Default:
Options:
0
0
1
2
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”