Parameter data in linear list format, Parameter data in linear list format -16 – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 70
3-16
Programming and Parameters
Parameter Data in Linear
List Format
No.
Name
Description
Values
Li
nka
b
le
Rea
d
-W
ri
te
Da
ta
T
yp
e
1
Motor NP Volts
Set to the motor nameplate rated volts.
Units:
Default:
Min/Max:
Volt
Calculated
75/705
✓ 16-bit
Integer
2
Motor NP FLA
Set to the motor nameplate rated full load amps. Range limited by three-second inverter
rating.
Units:
Default:
Min/Max:
Amps
Calculated
Calculated/Calculated
✓ Real
3
Motor NP Hertz
Set to the motor nameplate rated frequency.
Units:
Default:
Min/Max:
Hz
Calculated
2.0000/500.0000
✓ Real
4
Motor NP RPM
Set to the motor nameplate rated RPM.
Units:
Default:
Min/Max:
RPM
Calculated
1/30000
✓ 16-bit
Integer
5
Motor NP Power
Set to the motor nameplate rated power.
Units:
Default:
Min/Max:
Hp
Calculated
0.2500/3500.0000
✓ Real
6
Mtr NP Pwr Units
The power units shown on the motor nameplate.
Default:
Options:
0
0
1
Hp
Hp
W
7
Motor Poles
Set to the number of motor poles indicated on the motor nameplate. Only even numbers are
allowed.
Units:
Default:
Min/Max:
Pole
4
2/40
✓ 16-bit
Integer
8
Motor Inertia
Time, in seconds, for an uncoupled motor to accelerate from zero to base speed, at rated
motor torque. Calculated during autotune.
Units:
Default:
Min/Max:
Sec
0.400
0.0100/655.0000
✓ ✓ Real
9
Total Inertia
Time, in seconds, for a motor coupled to a load to accelerate from zero to base speed, at
rated motor torque. Calculated during autotune.
Units:
Default:
Min/Max:
Sec
2.0000
0.0100/655.0000
✓ ✓ Real
10
Speed Ref 1
Sets the speed reference that the drive should use when selected by Par 16 [Speed Ref Sel].
A value of 1.0 represents base speed of the motor.
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓ ✓ Real
11
Spd Ref1 Divide
Par 10 [Speed Ref 1] is divided by this number. This number can be used to scale the value
of Par 10 [Speed Ref 1].
Default:
Min/Max:
1.0000
-/+2200000000.0000
✓ ✓ Real
12
Speed Ref 2
Sets the speed reference that the drive should use when selected by Par 16 [Speed Ref Sel].
A value of 1.0 represents base speed of the motor.
Default:
Min/Max:
0.0000
-/+2200000000.0000
✓ ✓ Real
13
Spd Ref2 Multi
Par 12 [Speed Ref 2] is multiplied by this number. This number can be used to scale the
value of Par 12 [Speed Ref 2].
Default:
Min/Max:
1.0000
-/+2200000000.0000
✓ ✓ Real
14
Speed Ref 4
Sets the speed reference that the drive should use when selected by Par 16 [Speed Ref Sel].
Units:
Default:
Min/Max:
Comm Scale:
RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0
✓ ✓ Real
15
Speed Ref 5
Sets the speed reference that the drive should use when selected by Par 16 [Speed Ref Sel].
Units:
Default:
Min/Max:
Comm Scale:
RPM
0.0000
-/+14112.0000
Par 4[Motor NP RPM] = 1.0
✓ ✓ Real
16
Speed Ref Sel
Selects the source of the speed reference to the drive.
Default:
Options:
1
0
1
2
3
“Spd Ref DPI”
“Zero Speed”
4
“Spd Ref 4”
“Spd Ref 1
5
“Spd Ref 5”
“Spd Ref 2”
6
“Spd Ref DPI”
“Spd Ref 3
17
Jog Speed 1
Sets the speed reference that the drive should use when responding to bit 18 [Jog 1] of Par
152 [Applied LogicCmd].
Units:
Default:
Min/Max:
Comm Scale:
RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0
✓ ✓ Real
18
Jog Speed 2
Sets the speed reference that the drive should use when responding to bit 23 [Jog 2] of Par
152 [Applied LogicCmd].
Units:
Default:
Min/Max:
Comm Scale:
RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0
✓ ✓ Real
19
Atune Spd Ref
Sets the maximum speed of the motor during the Flux current and inertia tests.
Units:
Default:
Min/Max:
Comm Scale:
RPM
1499.4000
176.4000/1764.0000
Par 4 [Motor NP RPM] = 1.0
✓ Real