A-14
Supplemental Information
690 Volt AC Input Frames 5 and 6 Drive Protection Devices
540 Volt DC Input Frames 1…6 Drive Protection Devices
Drive
Catalog
Number
Fr
am
e
kW Rating
Input Ratings
Dual Element Time Delay
Fuse
Non-Time Delay Fuse
Circuit Breaker
(3)
Motor Circuit Protector
(5)
ND
HD
Amps
kVA
Min.
(1)
Max.
(2)
Min.
(2)
Max.
(3)
Max.
(4)
Max.
(5)
20DF052
5
45
–
46.9
59.5
60
110
60
175
175
–
–
37.5
40.1
48.0
50
90
50
150
150
–
20DF060
5
55
–
57.7
68.9
80
125
80
225
225
–
–
45
46.9
59.5
60
110
60
175
175
–
20DF082
5
75
–
79.0
94.4
100
200
100
375
375
–
–
55
57.7
68.9
80
125
80
225
225
–
20DF098
5
90
–
94.7
113
125
200
125
375
375
–
–
75
79.0
94.4
100
200
100
375
375
–
20DF119
6
110
–
115
138
150
250
150
400
–
–
–
90
92.9
113
125
200
125
375
–
–
20DF142
6
132
–
139
165.9
175
300
175
450
–
–
110
115
137
150
250
150
400
–
–
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive Catalog Number
Frame
kW Rating
DC Input Ratings
Fuse
Non-Time Delay Fuse
(2)
(2)
The power source to Common Bus inverters must be derived from AC voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC). Battery supplies or
MG sets are not included. The following devices were validated to break current of the derived power DC Bus: Disconnects: Allen-Bradley Bulletin No.
1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. Fuses: Bussmann Type JKS, all sizes;Type 170M, Case Sizes
1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please contact the factory.
ND
HD
Amps
20DC3P5
1
1.5
1.1
3.7
8
JKS-8
20DC5P0
1
2.2
1.5
5.3
10
JKS-10
20DC8P7
1
4
3.0
9.3
15
HSJ15
20DC011
1
5.5
4
12.6
20
HSJ20
20DC015
1
7.5
5.5
16.8
25
HSJ25
20DC022
1
11
7.5
24
40
HSJ40
20DC030
2
15
11
33.2
50
HSJ50
20DC037
2
18.5
15
40.9
70
HSJ70
20DC043
3
22
18.5
47.5
90
HSJ90
20DC056
3
30
22
61.9
100
HSJ100
20DC072
3
37
30
80.5
125
HSJ125
20DC085
4
45
37
95.1
150
HSJ150
20DH105
(1)
(1)
Also applies to “P” voltage class. Fuses must be applied in the (+) leg and (-) leg of the DC Common Bus.
5
55
–
120.2
175
HSJ175
–
45
95.1
175
HSJ175
20DH125
(1)
5
55
–
120.2
200
HSJ200
–
45
95.1
200
HSJ200
20DH140
5
75
–
159
250
HSJ250
–
55
120.2
250
HSJ250
20DH170
(1)
6
90
–
192
350
HSJ350
–
75
159
350
HSJ350
20DH205
(1)
6
110
–
226
350
HSJ350
–
90
192
350
HSJ350
20DH260
(1)
6
132
–
298
400
HSJ400
–
110
226
400
HSJ400