Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 38

1-24
Installation/Wiring
Table 1.L TB1 - Row B (Bottom) Terminals
Terminal
Signal
Description
Related
Pa
ra
m
et
er
B11
Analog Input #1 (-)
+/-10.0V DC or +/-1.0V DC bipolar,
differential input.
(1)
13 bit + sign,
20k ohm input impedance
800, 802,
803, 804,
805
B10
Analog Input #1 (+)
B9
Analog Input Shield
Optional connection point for
analog input shield.
(2)
B8
Analog Input #2 (-)
+/-10.0V DC or +/-1.0V DC bipolar,
differential input.
13 bit + sign,
20k ohm input impedance
806, 808,
809, 810,
811
B7
Analog Input #2 (+)
B6
Analog Output #1 (+)
+/-10.0V DCDC bipolar, differential
output, 11 bit + sign, 2k ohm
minimum load
812, 814,
815, 817,
818
B5
Analog Output #1 Return (-)
B4
Analog Output Shield
Optional connection point for
analog output shield.
B3
Analog Output #2 (+)
+/-10.0V DC bipolar, differential
output, 11 bit + sign, 2k ohm
minimum load
813, 819,
820, 822,
823,
B2
Analog Output #2 Return (-)
B1
Analog Output Shield
Optional connection point for
analog shields.
(1)
Analog Input Settings on page 1-32
for necessary dip switch settings.
(2)
Analog shields should connect to common at the signal source, if possible. Shields for signals from ungrounded devices, such as analog
tachometers, should connect to an analog shield terminal point at the drive.
11
10
9
8
7
6
5
4
3
B1
2