Us c – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 166
![background image](/manuals/577236/166/background.png)
A-2
Supplemental Information
Agency
Certification
The drive is designed to meet applicable requirements of the
following codes/standards:
IEC 61800-2 Adjustable speed electrical power drive systems -
General requirements
IEC 61800-5-1 Adjustable speed electrical power drive systems
- Safety requirements
NFPA 70 – US National Electric Code
NEMA 250 – Enclosures for Electrical Equipment
The drive is designed to meet applicable requirements of the
following codes/standards:
IEC 61800-2 Adjustable speed electrical power drive systems -
General requirements
IEC 61800-5-1 Adjustable speed electrical power drive systems
- Safety requirements
NFPA 70 - US National Electrical Code
UL and cUL Listed to UL508C and CAN/CSA - 22.2 No. 14-95
UL and cUL Listed to UL508C and CAN/CSA - 22.2 No. 14-95
Marked for all applicable European Directives
EMC Directive (89/336/EEC)
Emissions
EN 61800-3 Adjustable Speed electrical power drive
systems Part 3
Immunity
EN 61800-3 Second Environment, Restricted Distribution
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power
Installations
Marked for all applicable European Directives
EMC Directive (89/336/EEC)
Emissions
EN 61800-3 Adjustable Speed electrical power drive
systems Part 3
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power
Installations
TUV Rheinland (applies to frames 1 - 6, 200/400V, and frames 5
& 6, 690V only)
TUV Functional Safety Report only for frames 1 - 4, 600V (no FS
mark on the label)
TUV functional safety report only (no FS mark on the label)
Environment Altitude:
1000 m (3300 ft.) max. without derating
1000 m (3300 ft) max. without derating
Surrounding Air Temperature
without Derating:
Based on drive rating, refer to Drive Frame chapters
Open Type:
0 to 50° C (32 to 122° F)
IP20:
0 to 50° C (32 to 122° F)
NEMA Type 1:
0 to 40° C (32 to 104 ° F)
IP56, NEMA Type 4X:
0 to 40 ° C (32 to 104 ° F)
Note: Frames 9 & 10 are rated 0 to 40 ° C (32 to 104 ° F)
surrounding air.
Storage Temperature (all
const.):
-40 to 70° C (-40 to 158° F)
–40 to 70 degrees C (–40 to 158 degrees F)
Relative Humidity:
5 to 95% non-condensing
5 to 95% non-condensing
Shock:
10G peak for 11 ms duration (+/- 1.0 ms)
15G peak for 11ms duration (
±1.0 ms)
Vibration:
0.152 mm (0.006 in.) displacement, 1G peak, 5.5 Hz
2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6
Atmosphere
—
Important: Drive must not be installed in an area where the
ambient atmosphere contains volatile or corrosive gas, vapors
or dust. If the drive is not going to be installed for a period of
time, it must be stored in an area where it will not be exposed to
a corrosive atmosphere.
Electrical
AC Input
Voltage Tolerance:
See
Input Voltage Range/Tolerance on page C-1
for Full Power
and Operating Range
—
Frequency Tolerance:
47-63 Hz
47-63 Hz.
Input Phases:
Three-phase input provides full rating for all drives. Single-phase
operation provides 50% of rated current.
Three-phase input provides full rating for all drives.
Single-phase operation provides 50% of rated current.
DC Input
Voltage Tolerance
+/- 10% of Nominal Bus Voltage (above)
—
Displacement Power Factor:
0.98 across speed range
0.98 across speed range
Efficiency:
97.5% at rated amps, nominal line volts.
97.5% at rated amps, nominal line volts.
Max. Short Circuit Current
Rating:
Using Recommended Fuse
or Circuit Breaker Type
Maximum short circuit current rating to match specified fuse/
circuit breaker capability.
≤ 200,000 Amps
≤ 200,000 Amps
Maximum Drive to Motor Power
Ratio
The drive to motor rating cannot exceed a 2:1 ratio
The drive to motor rating cannot exceed a 2:1 ratio
Category
Specification
Frames 1-6 (690V Drive frames 5 & 6 only)
Frames 9 & up
UL
US
C
®
TUV
Rheinland
Product Safety
.
.
Production inspected
W
E
C
TUV
Rheinland
.
.
Functional
Safety
Bauart geprüft
Type approved
EN 50178