Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 177
Supplemental Information
A-13
20DE099
5
100
–
92.9
96.6
125
200
125
375
375
150
–
–
–
–
–
75
72.3
75.1
100
175
100
300
300
100
–
–
–
–
20DE125
6
125
–
117
121.6
150
250
150
375
375
250
–
–
–
–
–
100
93
96.6
125
200
125
375
375
150
–
–
–
–
20DE144
6
150
–
135
140.5
175
300
175
400
400
250
–
–
–
–
–
125
117
121.6
150
275
150
375
375
250
–
–
–
–
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(6)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(8)
The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See
Bulletin 140M Motor Protection Circuit Breakers Application Ratings
.
(9)
When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.
Drive
Catalog
Number
Fr
am
e
HP Rating
Input Ratings Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND
HD
Amps
kVA
Min.
(1)
Max.
(2)
Min.
(3)
Max.
(4)
Max.
(4)
Max.
(6)
Available Catalog Numbers
(8)
Minimum Enclosure
Volume (in.
3
)
(9)