beautypg.com

Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 177

background image

Supplemental Information

A-13

20DE099

5

100

92.9

96.6

125

200

125

375

375

150

75

72.3

75.1

100

175

100

300

300

100

20DE125

6

125

117

121.6

150

250

150

375

375

250

100

93

96.6

125

200

125

375

375

150

20DE144

6

150

135

140.5

175

300

175

400

400

250

125

117

121.6

150

275

150

375

375

250

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

(6)

Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.

(7)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.

(8)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M Motor Protection Circuit Breakers Application Ratings

.

(9)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.

Drive

Catalog

Number

Fr

am

e

HP Rating

Input Ratings Dual Element

Time Delay Fuse

Non-Time Delay

Fuse

Circuit

Breaker

(3)

Motor

Circuit

Protector

(5)

140M Motor Starter with Adjustable Current Range

(6)(7)

ND

HD

Amps

kVA

Min.

(1)

Max.

(2)

Min.

(3)

Max.

(4)

Max.

(4)

Max.

(6)

Available Catalog Numbers

(8)

Minimum Enclosure
Volume (in.

3

)

(9)