Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 176
![background image](/manuals/577236/176/background.png)
A-12
Supplemental Information
480 Volt AC Input Frames 9…11 Drive Protection Devices
600 Volt AC Input Frames 1…6 Drive Protection Devices
Drive Catalog
Number
Fr
am
e
HP Rating
Input
Ratings
Dual Element Time Delay Fuse
Non-Time Delay Fuse
Bussmann Style Semi-
Conductor Fuse
Circuit
Breaker
(3)
Motor Circuit
Protector
(5)
ND
HD
Amps
Min.
(1)
Max.
(2)
Min.
(1)
Max.
(3)
Max.
(4)
Max.
(5)
20DD261
9
200
-
252
350
550
350
700
170M5813
700
400
-
150
207
275
450
275
600
170M5813
600
300
20DD300
9
250
-
290
400
650
400
900
170M5813
900
400
-
200
247
350
550
350
700
170M5813
700
400
20DD385
10
300
-
372
500
850
500
1100
170M5813
1100
600
-
250
302
400
650
400
900
170M5813
900
400
20DD460
10
350
-
444
600
1000
600
1300
170M8547
1300
600
-
300
388
500
850
500
1100
170M8547
1100
600
20DD500
10
450
-
483
650
1000
650
1500
170M8547
1500
700
-
350
423
550
900
550
1200
170M8547
1200
600
20DD590
11
500
-
570
750
(1 per phs)
375
(2 per phs)
1300
750
(1 per phs)
375
(2 per phs)
1700
170M5813
1700
800
-
450
524
700
(1 per phs)
350
(2 per phs)
1100
700
(1 per phs)
350
(2 per phs)
1500
170M5813
1500
700
20DD650
11
500
-
628
800
(1 per phs)
400
(2 per phs)
1400
800
(1 per phs)
400
(2 per phs)
1900
170M5813
1900
800
-
500
594
750
(1 per phs)
375
(2 per phs)
1300
750
(1 per phs)
375
(2 per phs)
1700
170M5813
1700
800
20DD730
11
600
-
705
900
(1 per phs)
450
(2 per phs)
1600
900
(1 per phs)
450
(2 per phs)
2100
170M5813
2100
900
-
500
655
850 (1 per phs)
425 (2 per phs)
1400
850
(1 per phs)
425
(2 per phs)
1900
170M5813
1900
900
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive
Catalog
Number
Fr
am
e
HP Rating
Input Ratings Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND
HD
Amps
kVA
Min.
(1)
Max.
(2)
Min.
(3)
Max.
(4)
Max.
(4)
Max.
(6)
Available Catalog Numbers
(8)
Minimum Enclosure
Volume (in.
3
)
(9)
20DE1P7
1
1
0.75
1.3
1.4
2
4
2
6
15
3
M-C2E-B16
–
–
7269
20DE2P7
1
2
1.5
2.1
2.1
3
6
3
10
15
3
M-C2E-B25
–
–
7269
20DE3P9
1
3
2
3.0
3.1
6
9
6
15
15
7
M-C2E-B40
M-D8E-B40
–
7269
20DE6P1
1
5
3
5.3
5.5
9
12
9
20
20
15
–
M-D8E-B63
–
7269
20DE9P0
1
7.5
5
7.8
8.1
10
20
10
35
30
15
–
M-D8E-C10
M-F8E-C10
7269
20DE011
1
10
7.5
9.9
10.2
15
25
15
40
40
15
–
M-D8E-C10
M-F8E-C10
7269
20DE017
1
15
10
15.4
16.0
20
40
20
60
50
20
–
M-D8E-C16
M-F8E-C16
7269
20DE022
2
20
15
20.2
21.0
30
50
30
80
80
30
–
–
M-F8E-C25
7269
20DE027
2
25
20
24.8
25.7
35
60
35
100
100
50
–
–
M-F8E-C25
7269
20DE032
3
30
25
29.4
30.5
40
70
40
125
125
50
–
–
M-F8E-C32
13630
20DE041
3
40
30
37.6
39.1
50
90
50
150
150
100
–
–
–
–
20DE052
3
50
40
47.7
49.6
60
110
60
200
200
100
–
–
–
–
20DE062
4
60
50
58.2
60.5
80
125
80
225
225
100
–
–
–
–
20DE077
5
75
–
72.3
75.1
90
150
90
300
300
100
–
–
–
–
–
60
58.2
60.5
90
125
90
250
250
100
–
–
–
–