Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 175
![background image](/manuals/577236/175/background.png)
Supplemental Information
A-11
480 Volt AC Input Frames 1…6 Drive Protection Devices
20DC650
11 355
-
655
850 (1 per phs)
425 (2 per phs)
1400
850 (1 per phs)
425 (2 per phs)
1900
170M5813
1900
1000
-
315
594
750 (1 per phs)
375 (2 per phs)
1300
750 (1 per phs)
375 (2 per phs)
1700
170M5813
1700
800
20DC730
11 400
-
735
1000 (1 per phs)
500 (2 per phs)
1600
1000 (1 per phs)
500 (2 per phs)
2100
170M5813
2100
1200
-
355
655
850 (1 per phs)
425 (2 per phs)
1400
850 (1 per phs)
425 (2 per phs)
1900
170M5813
1900
1000
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive Catalog
Number
Fr
am
e
kW Rating
Input
Ratings
Dual Element Time Delay Fuse
Non-Time Delay Fuse
Bussmann Style Semi-
Conductor Fuse
Circuit
Breaker
(3)
Motor Circuit
Protector
(5)
ND
HD
Amps
Min.
(1)
Max.
(2)
Min.
(1)
Max.
(3)
Max.
(4)
Max.
(5)
Drive
Catalog
Number
Fr
am
e
HP Rating Input Ratings Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND
HD
Amps
kVA
Min.
(1)
Max.
(2)
Min.
(3)
Max.
(4
)
Max.
(4)
Max.
(6)
Available Catalog Numbers
(8)
Minimum Enclosure
Volume (in.
3
)
(9)
20DD2P1
1
1
0.7
5
1.6
1.4
3
6
3
8
15
3
M-C2E-B25
–
–
7269
20DD3P4
1
2
1.5
2.6
2.2
4
8
4
12
15
7
M-C2E-B40
M-D8E-B40
–
7269
20DD5P0
1
3
2
3.9
3.2
6
10
6
20
20
7
M-C2E-B63
M-D8E-B63
–
7269
20DD8P0
1
5
3
6.9
5.7
10
15
10
30
30
15
M-C2E-C10
M-D8E-C10
M-F8E-C10
7269
20DD011
1
7.5
5
9.5
7.9
15
20
15
40
40
15
M-C2E-C16
M-D8E-C16
M-F8E-C16
7269
20DD014
1
10
7.5
12.5
10.4
17.5
30
17.5
50
50
20
M-C2E-C16
M-D8E-C16
M-F8E-C16
7269
20DD022
1
15
10
19.9
16.6
25
50
25
80
80
30
–
M-D8E-C25
M-F8E-C25
7269
20DD027
2
20
15
24.8
20.6
35
60
35
100
100
50
–
–
M-F8E-C32
7269
20DD034
2
25
20
31.2
25.9
40
70
40
125
125
50
–
–
M-F8E-C45
7269
20DD040
3
30
25
36.7
30.5
50
90
50
150
150
50
–
–
M-F8E-C45
13630
20DD052
3
40
30
47.7
39.7
60
110
60
200
200
70
–
–
–
–
20DD065
3
50
40
59.6
49.6
80
125
80
250
250
100
–
–
–
–
20DD077
4
60
–
72.3
60.1
100
170
100
300
300
100
–
–
–
–
–
50
59.6
49.6
80
125
80
250
250
100
–
–
–
–
20DD096
5
75
–
90.1
74.9
125
200
125
350
350
125
–
–
–
–
–
60
72.3
60.1
100
170
100
300
300
100
–
–
–
–
20DD125
5
100
–
117
97.6
150
250
150
500
375
150
–
–
–
–
–
75
90.1
74.9
125
200
125
350
350
125
–
–
–
–
20DD156
6
125
–
146.5
121.7
200
350
200
600
450
250
–
–
–
–
–
100
131
97.6
175
250
175
500
375
250
–
–
–
–
20DD180
6
150
–
169
140.5
225
400
225
600
500
250
–
–
–
–
–
125
147
121.7
200
350
200
600
450
250
–
–
–
–
20DD248
6
200
232.8
188
300
550
300
700
700
400
–
–
–
–
150
169
140.5
225
400
225
600
500
250
–
–
–
–
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(6)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(8)
The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See
Bulletin 140M Motor Protection Circuit Breakers Application Ratings
.
(9)
When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.