Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 103

Programming and Parameters
3-49
375
Inv OT Pend Cnfg
Enter a value to configure the drive's response to a Inverter Over-Temperature (OT)
Pending exception event. This event is triggered when the Inverter NTC (Temperature
protection) function detects the heat-sink temperature reaches to the overload warning
level.
• 0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
1
0
1
2
3
4
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
376
Inv OL Pend Cnfg
Enter a value to configure the drive's response to an Inverter Overload (OL) Pending
exception event. This event is triggered when one of the Inverter Protection
Current-Over-Time functions (Open Loop or Closed Loop) detects current and
temperature at warning levels.
• 0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
1
0
1
2
3
4
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
377
Inv OL Trip Cnfg
Enter a value to configure the drive's response to an Inverter Overload (OL) Trip
exception event. This event is triggered when one of the Inverter Protection
Current-Over-Time functions (Open Loop or Closed Loop) detects current and
temperature at a fault level.
• 0 “Ignore” Configures the drive to continue running, as normal, when this event occurs
• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
Default:
Options:
1
0
1
2
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
378
Interp Flt Cnfg
Enter a value to configure the drive's response when a Synchronization input to the
Interpolator has been lost or has become excessively irregular.
• 0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
2
0
1
2
3
4
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
379
Ext Flt/Alm Cnfg
Enter a value to configure the drive's response to an External Input exception event. The
event is triggered by a digital input that is configured for auxiliary fault or auxiliary aux
fault by choosing option 11 “Aux Fault” or 12 “AuxFault Inv” in Pars 838 [DigIn 1 Sel], 839
[DigIn 2 Sel], or 840 [DigIn 3 Sel].
• 0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
• 3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
• 4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
2
0
1
2
3
4
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
381
PreChrg Err Cnfg
Enter a value to configure the drive's response to a Precharge Error exception event.
• 0 “Ignore” Configures the drive to continue running, as normal, when this event occurs
• 1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
• 2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
Default:
Options:
2
0
1
2
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”