Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 131
Programming and Parameters
3-77
832
DigIn2 User Data
Provides a source of data controlled by bit 2 [DigIn 2] of Par 824 [Local I/O Status].
Link to a Read-Write parameter and enter a value of 13 in Par 839 [DigIn2 Sel] to activate
this function.
Default:
Min:
Max:
Comm Scale:
00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111
Inputs & Outputs Digital Inputs
32-bit
Boolean
833
DigIn2 Debounce
Sets the value of the debounce filter for Digital Input 2. The filter requires the input signal
to be stable for the specified time period. Input transitions within the filter time setting will
be ignored.
Units:
Default:
Min/Max:
mSec
8.0000
0.000015.5000
✓ ✓ Real
834
DigIn3 Data
Sets the value of Par 836 [DigIn3 User Data], except for the bit controlled by bit 3 [DigIn 3]
of Par 824 [Local I/O Status].
Default:
Min:
Max:
00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111
✓ ✓ 32-bit
Boolean
835
DigIn3 Bit
Selects the bit, in Par 836 [DigIn 3 User Data], which is controlled by bit controlled by bit 3
[DigIn 3] of Par 824 [Local I/O Status].
Default:
Min/Max:
0
-32/31
✓ ✓ 16-bit
Integer
836
DigIn3 User Data
Provides a source of data controlled by bit 3 [DigIn 3] of Par 824 [Local I/O Status].
Link to a Read-Write parameter and enter a value of 13 in Par 840 [DigIn3 Sel] to activate
this function.
Default:
Min:
Max:
00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111
32-bit
Boolean
837
DigIn3 Debounce
Sets the value of the debounce filter for Digital Input 3. The filter requires the input signal
to be stable for the specified time period. Input transitions within the filter time setting will
be ignored.
Units:
Default:
Min/Max:
mSec
8.0000
0.0000/15.5000
✓ ✓ Real
838
DigIn1 Sel
Enter or write a value to select the function of Digital Input 1.
Default:
Options:
0
0
1
2
3
4
5
6
7
“Not Used”
“Not Used”
8
“Fwd/Reverse”
“Normal Stop”
9
“CurLim Stop”
“Start”
10 “Coast Stop”
“Run”
11 “Aux Fault”
“Clear Faults”
12 “AuxFault Inv”
“Stop - CF”
13 “User Select”
“Jog 1”
14 “PreChrg/Disc”
“Jog 2”
839
DigIn2 Sel
Enter or write a value to select the function of Digital Input 2.
Default:
Options:
4
0
1
2
3
4
5
6
7
8
9
10
11
12
13
“Not Used”
“Not Used”
14 “Reserved”
“Normal Stop”
15 “Reserved”
“Start”
16 “Reserved”
“Run”
17 “Reserved”
“Clear Faults”
18 “Reserved”
“Stop - CF”
19 “Reserved”
“Jog 1”
20 “Reserved”
“Jog 2”
21 “Reserved”
“Fwd/Reverse”
22 “Reserved”
“CurLim Stop”
23 “Logix Motion”
“Coast Stop”
24 “+Hrd OvrTrvl”
“Aux Fault”
25 “-Hrd OvrTrvl”
“AuxFault Inv”
“User Select”
840
DigIn3 Sel
Enter or write a value to select the function of Digital Input 3.
Default:
Options:
0
0
1
2
3
4
5
6
7
8
9
10
11
12
“Not Used”
“Not Used”
13 “User Select”
“Normal Stop”
14 “Reserved”
“Start”
15 “Reserved”
“Run”
16 “Reserved”
“Clear Faults”
17 “Reserved”
“Stop-CF”
18 “Reserved”
“Jog 1”
19 “Reserved”
“Jog 2”
21 “Reserved”
“Fwd/Reverse”
22 “Reserved”
“CurLim Stop”
23 “Logix Motion”
“Coast Stop”
24 “+Hrd OvrTrvl”
“Aux Fault”
25 “-Hrd OvrTrvl”
“AuxFault Inv”
841
Relay Out Data
Link a word to this parameter that will control the Relay Output. The bit within the selected
word that will control the Relay Output is set by Par 842 [Relay Out Bit].
Default:
Min:
Max:
00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111
✓ ✓ 32-bit
Boolean
842
Relay Out Bit
Selects the bit, from the word linked to Par 841 [Relay Out Data] that will change the
status of the Relay Output (e.g., when Par 842 [Relay Out Bit] equals 0, bit 0 of Par 841
[Relay Out Data] will control the Relay Output).
Default:
Min/Max:
0
-32/31
✓ ✓ 16-bit
Integer
843
DigOut 1 Data
Link a word to this parameter that will control Digital Output 1. The bit within the selected
word that will control Digital Output 1 is set by Par 844 [DigOut 1 Bit].
Default:
Min:
Max:
00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111
✓ ✓ 32-bit
Boolean
No.
Name
Description
Values
Li
nkab
le
Read
-Wr
it
e
Da
ta
T
ype