Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual
Page 174
A-10
Supplemental Information
400 Volt AC Input Frames 9…11 Drive Protection Devices
20DC085
(1)
4
45
–
81.4
56.4
110
200
110
300
300
150
–
–
–
–
–
37
68.9
47.8
90
175
90
275
300
100
–
–
–
–
20DC105
5
55
–
100.5
69.6
125
225
125
400
300
150
–
–
–
–
45
81.4
56.4
110
175
110
300
300
150
–
–
–
–
20DC125
5
55
–
121.1
83.9
150
275
150
500
375
250
–
–
–
–
–
45
101
63.7
125
200
125
375
375
150
–
–
–
–
20DC140
5
75
–
135.6
94
200
300
200
400
400
250
–
–
–
–
–
55
121
69.6
150
225
150
300
300
150
–
–
–
–
20DC170
6
90
–
164.6
114
250
375
250
600
500
250
–
–
–
–
–
75
136
94
200
300
200
550
400
250
–
–
–
–
20DC205
(2)
6
110
–
198.5
138
250
450
250
600
600
400
–
–
–
–
–
90
164
114
250
375
250
600
500
250
–
–
–
–
20DC260
6
–
254.7
166
350
550
350
750
750
400
–
–
–
–
–
110
199
138
250
450
250
600
600
400
–
–
–
–
(1)
20DC085 current rating is limited to 45 degrees C ambient.
(2)
20DC205 current rating is limited to 40 degrees C ambient.
(3)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(5)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(6)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(7)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(8)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(9)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.
(10) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See
Bulletin 140M Motor Protection Circuit Breakers Application Ratings
.
(11) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal
considerations may require a larger enclosure.
Drive
Catalog
Number
Fr
am
e
kW Rating
Input
Ratings
Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(5)
Motor
Circuit
Protector
(7)
140M Motor Starter with Adjustable Current Range
(8)(9)
ND
HD
Amps
kVA
Min.
(3)
Max.
(4)
Min.
(5
)
Max.
(6)
Max.
(6)
Max.
(8)
Available Catalog Numbers
(10)
Minimum Enclosure
Volume (in.
3
)
(11)
Drive Catalog
Number
Fr
am
e
kW Rating
Input
Ratings
Dual Element Time Delay Fuse
Non-Time Delay Fuse
Bussmann Style Semi-
Conductor Fuse
Circuit
Breaker
(3)
Motor Circuit
Protector
(5)
ND
HD
Amps
Min.
(1)
Max.
(2)
Min.
(1)
Max.
(3)
Max.
(4)
Max.
(5)
20DC261
9
132
-
263
350
550
350
700
170M5813
700
400
-
110
207
275
450
275
600
170M5813
600
300
20DC300
9
160
-
302
400
650
400
900
170M5813
900
400
-
132
247
350
500
350
700
170M5813
700
400
20DC385
10 200
-
388
500
850
500
1100
170M5813
1100
600
-
160
302
400
650
400
900
170M5813
900
400
20DC460
10 250
-
463
600
1000
600
1300
170M8547
1300
600
-
200
388
500
850
500
1100
170M8547
1100
600
20DC500
10 250
-
504
650
1100
650
1500
170M8547
1500
700
-
250
423
550
900
550
1200
170M8547
1200
600
20DC590
11 315
-
594
750 (1 per phs)
375 (2 per phs)
1300
750 (1 per phs)
375 (2 per phs)
1700
170M5813
1700
800
-
250
524
700 (1 per phs)
350 (2 per phs)
1100
700 (1 per phs)
350 (2 per phs)
1500
170M5813
1500
700