Security tab settings – Maple Systems 5000HD Series User Manual
Page 120

114
EZwarePlus Programming Manual
1010-1015, Rev. 03
Security tab settings:
The Security tab is used to set up a table of users, user levels (access classes), and passwords. When General
mode is selected, up to 12 users can be individually enabled, and each has a unique password and
combination of any six access classes (A-F). Only numbers are allowed for passwords. When an object is
created, it can be assigned an access class. When that object is activated (for example, a button is touched),
the HMI compares the access classes allowed for the currently logged-in user to the access class specified for
the object. If the access class of the object is within the classes allowed, the object’s action is executed.
The access class for an object is configured in the User restriction section of the Security tab for that object.
So, for example, if you wish to set the access class for a set bit object, click on the Security tab of that object’s
properties dialog, as shown below: