Chapter 4 Installing the Level 2R Storage System

File System Server
Configuration

This page checks on the
configuration of the media
server in one of its main
roles as a file system server.
The media server also
functions as a file system
client, which is also checked
from this page.

It is not necessary to bind
LUNs or create a file system,
since this task was
completed when you
configured the previous
media server.

Click

Check

. Confirm a “… default.cfg file copied…” message. When

the wizard reports that the configuration check is successful, click

Next

.

and

Yes

to confirm copying default.cfg to the other server.

If you get a “The V: will not be available until this device is rebooted…”
message, you can safely continue with this procedure and follow the
instructions related to this message later in the procedure.

iSCSI Bridge Server
Configuration

This page manages the
components that bridge
between iSCSI (the GigE
media network) and the
Fibre Channel connection to
the RAID storage. You
configure network settings
on the iSCSI adapters and
the page validates that the
Fibre Channel adapter is in
place and that the media
LUNs are visible as iSCSI
targets.

NOTE: The iSCSI
adapters on this
server must be on a
different subnet
than those on its
redundant server
partner.

For Level 2 redundant, select

Backup

.

Select an iSCSI adapter and click

Modify

. A network configuration

dialog box opens. Enter the media network IP address and subnet mask
and click

Apply

. Do the same for the other iSCSI adapter.

To verify drives, click

Check

then

View Target Drives

. You should see

all your media drives listed.
Click

Next

.

On this page…

Do this…