Site Controller won't communicate. All loop device are down. PC is booted and runnning.
Error being displayed when the CFN3 application is started; Read timeout, inctl=XXXX
outctl=XXXX.

Possible Cause

Checks

Corrective Action

Site Controller board set not
installed or not seated
properly.

Check if board set is installed
or seated properly.

Install or re-install board set
(always remember to shut
down PC before
adding/removing boards).

Incorrect power fail jumper.

Check K3 on Site Comm CPU
board. There should be a 3
position jumper on K3.

Correct as needed.

Site memory I/O switches set
wrong.

Check switch S1 on SC-
memory I/O.

All switches are normally
closed.

Site Controller memory needs
complete reinitialization.

None

Open the SC III tower. On the
Memory Board DIP switch S1,
set positions 1, 2, and 4 to
open (up). On the Comm
board, remove the K4 jumper.
On the keyboard, press ALT-
N. At the Debug >> prompt,
press ! Let the system run for
about 20 seconds. Press
ENTER. Return the switches
and the jumper to their proper
positions. On the keyboard,
press ALT-N. The site should
come back up.
NOTE: It is normal to get
read/write timeout errors
during this process, but if the
errors continue after the last
ALT-N, the problem has not
been corrected.

Defective Site III board set.

None.

Replace board set.