2.4 Instruction Details
1
2
3-67
Chapter 2 Instructions
Example
Coding
Timing diagram (TMR000 #00010 and 0500 in the above example)
•
0500 and 0501 turn ON 1 second and 3.5 seconds respectively after 0000 turns
ON.
•
TMR000 is a subtraction timer. When the current value reaches "#00000",
contact T000 turns ON, and then output relay 0500 turns ON.
•
When input relay 0000 turns OFF, contact T000 and T001 turn OFF and the
current values of TMR000 and TMR001 are reset.
Note 1: The TMR number cannot be the same as any other TMS, TMH, TMR, C, or UDC
instructions in the same program.
Note 2: The current value of TMR is not retained but is reset to the preset value if a power
failure occurs or if power is turned OFF.
Tips
•
When the number specified by TMR is used as a contact (T000 in the above
example), this contact can be used as many times as desired. It can also be
used as both N.O. and N.C. contacts.
•
Timer accuracy = 0.1 sec. + (1 scan time) (max.)
Operands
Key operation
TMR: 0.1-s Timer
Sets a 16-bit on-delay timer that counts
down in 0.1-s decrements.
*1 0.1 s x 10 = 1 s
*2 0.1 s x 35 = 3.5 s
TMR
(
T
)
#ddddd
Txxx
0000
T000
T001
0500
0501
#00010
T000
#00035
T001
Preset value: 1 s
Preset value: 3.5 s
Line No.
Instruction
Operand
0000
LD
0000
0001
TMR
000 #00010*
1
0002
TMR
001 #00035*
2
0003
LD
T000
0004
OUT
0500
0005
LD
T001
0006
OUT
0501
OFF
ON
ON
#00010
#00000
Output 0500
Scan
Input 0000
Current
value of
TMR000
TMR
(
T
)
Operand
(TMR No.)
Operand
(Preset value)
ENT
R-SRCH
:
TMR
Visual KV
KV-300
KV-10/16
KV-24/40/80
No.: 000 to 249
No.: 000 to 249
No.: 000 to 063
No.: 000 to 119
Preset value:
Preset value:
Preset value:
Preset value:
#00000 to #65535
#00000 to #65535
#00000 to #65535
#00000 to #65535
KVNKA Chap 02_4aP.p65
08.3.11, 11:57 AM
67