2.4 Instruction Details
3-182
2
Chapter 2 Instructions
0400
LDA
C001
STA
2002
0001
TBIN
#09999
C001
0000
Line No.
Instruction
Operand
0000
LD
2002
0001
LDA
0400
0002
CON
0003
TBIN
0004
CON
0005
STA
C001
0006
LDB
0001
0007
C
001 #09999 0000
Converts data of 0400 to 0415 to BIN data and writes
into C001.
Sets C001
■ Output of 8-digit BCD data
Outputs the calculated product of DM0000 x DM0001 (0 to 99999999) in BCD of 8
digits at maximum as below:
High-order 4-digit BCD data
➞ To 0600 to 0615
Low-order 4-digit BCD data
➞ To 0500 to 0515
Coding
Application of TBIN instruction
■ Input of 4-digit BCD data
Sets 4 digits of the BCD digital switch (0400 to 0415) as the counter C001 value.
Coding
DM0000
LDA
DM0001
MUL
DM0101
STA
#10000
DIV
TM01
LDA
TBCD
0500
STA
2002
DM0101
LDA
TBCD
0600
STA
TM00
DM0000 x DM0001 =
TM00
0600 to 0615
0500 to 0515
... TM01
÷ #10000
=
Display
Internal register
High-order 4 digits Low-order 4 digits
High-order 4 digits
Internal register
Internal register
TM00
Low-order 4 digits
Remainder
High-order 4 digits
Low-order 4 digits
Line No.
Instruction
Operand
Line No.
Instruction
Operand
0000
LD
2002
0010
CON
0001
LDA
DM0000
0011
TBCD
0002
CON
0012
CON
0003
MUL
DM0001
0013
STA
0500
0004
CON
0014
CON
0005
DIV
#10000
0015
LDA
DM0101
0006
CON
0016
CON
0007
STA
DM0101
0017
TBCD
0008
CON
0018
CON
0009
LDA
TM01
0019
STA
0600
TBCD / @TBCD / TBIN / @TBIN
KVNKA Chap 02_4dP.p65
08.3.11, 0:04 PM
182