8.2 Details
3-355
1
8
Chapter 8 Programming Examples
a
f
b
e
c
g
d
a. 7500
b. 7501
c. 7502
d. 7503
e. 7504
f. 7505
g. 7506
Application of MPX instruction
■ Display of 7-segment LED
Displays the current value of counter C000 to the 7-segment LED.
Outputs from 7500 to 7571.
Connection of 7 segments
Connect each of 7 segments to output relays as shown below:
Ladder diagram
Coding
1000
1004
1005
1006
STA
7500
LDA
$003F
1001
STA
7500
LDA
$0006
1002
STA
7500
LDA
$005B
1003
STA
7500
LDA
$004F
1007
STA
7500
LDA
$0007
C000
#00009
C000
STA
1000
MPX
#0
LDA
C000
0000
Converts the counter value to 16-bit
data using the MPX instruction.
Auto reset counter
STA
7500
LDA
$0066
STA
7500
LDA
$006D
STA
7500
LDA
$007D
Sends internal register data to
output relays starting from 7500.
1008
STA
7500
LDA
$007F
1009
STA
7500
LDA
$006F
0
1
2
3
4
5
6
7
8
9
7-segment display
Line No. Instruction
Operand
0000
LDB
C000
0024
LD
1004
0001
C
000 #00009 0000
0025
LDA
$0066
0002
CON
0026
CON
0003
LDA
C000
0027
STA
7500
0004
CON
0028
LD
1005
0005
MPX
#0
0029
LDA
$006D
0006
CON
0030
CON
0007
STA
1000
0031
STA
7500
0008
LD
1000
0032
LD
1006
0009
LDA
$003F
0033
LDA
$007D
0010
CON
0034
CON
0011
STA
7500
0035
STA
7500
0012
LD
1001
0036
LD
1007
0013
LDA
$0006
0037
LDA
$0007
0014
CON
0038
CON
0015
STA
7500
0039
STA
7500
0016
LD
1002
0040
LD
1008
0017
LDA
$005B
0041
LDA
$007F
0018
CON
0042
CON
0019
STA
7500
0043
STA
7500
0020
LD
1003
0044
LD
1009
0021
LDA
$004F
0045
LDA
$006F
0022
CON
0046
CON
0023
STA
7500
0047
STA
7500