6.3 Positioning Control
KV
-300
KV-10/80
3-301
1
6
Chapter 6 Interrupts, High-speed Counters, Positioning Control
15000
17500
8000
2000
300
0
15000
Ramp-up/down control
When start switch 0002 is turned ON, 0500 outputs 100000 pulses under the
following conditions: start frequency 1 kHz, run frequency 5 kHz, and acceleration/
deceleration time 3 s.
Turn ON 0001 to decelerate and stop pulse output. When 0000 is turned ON, pulse
output is immediately stopped.
Application example of stepping motor control
Assume a program that can be controlled both automatically and manually.
In automatic mode, the system runs as shown in the chart below after 0000 is turned
ON.
In manual mode, the system goes forward while 0008 is ON and rearward while
0009 is ON. It returns to the origin when 0007 turns ON.
A pulse is output from 0500. Reverse the rotation direction by turning ON/OFF 0502.
The system is equipped with an origin sensor (0002), forward end limit (0006), and
rearward end limit (0004).
0002
DW
DW
DW
DW
DW
2008
EI
#01000 #05000 #03000 #00001 #34464 2310
0001
2308
END
INT
0000
2002
RES
2309
RET1
ENDH
DM9408 DM9409 DM9410 DM9411 DM9412
0001
0002
0003
0004
0005
0006
0007
0008
Enables interrupt when starting operation.
This is required to allow emergency stop
operation.
Sets parameters and simultaneously
starts pulse.
Decelerates and stops pulse.
Executes emergency stop sequence with
interrupt progaram.