KEYENCE Visual KV Series User Manual
Page 166

2.4 Instruction Details
3-142
2
Chapter 2 Instructions
■ Transferring the current counter value to data memory (DM)
Coding
Description
In step
a)
, the C010 current value is transferred via the internal register and stored
into DM0000, throughout the operation.
■ Transferring the contents of data memory as a setting value for a timer
Coding
Description
•
In step
a)
, contents of DM0010 is transferred to T002 via the internal register for
use as the T002 preset value, when 0002 is ON.
•
In step
b)
, contents of DM0011 is transferred to T002 via the internal register for
use as the T002 preset value, when 0002 is OFF.
•
Although the preset value of T002 is #00010 in the above example, any value
except #00000 can be given because the preset value is changed to the speci-
fied value by turning ON/OFF 0002. Once the counter value has been changed,
the changed value will be stored until it is changed again.
•
The setting values of timers and counters are reset to the original setting values
after the power is turned OFF once and then ON again.
Note 1: If an STA instruction is executed when the current value is larger than the
preset value, the current value will be changed to the preset value.
Note 2: Do not change the setting value of T002 to "#00000".
The C010 current value is transferred to DM0000.
0001
2002
C010
LDA
DM0000
STA
#09999
C010
0000
a)
Line No.
Instruction
Operand
0000
LDB
0001
0001
C
010 #099999 0000
0002
LD
2002
0003
LDA
C010
0004
CON
0005
STA
DM0000
0002
T002
0500
b)
DM0010
LDA
T002
STA
0002
0003
DM0011
LDA
T002
STA
#00010
T002
a)
Line No.
Instruction
Operand
Line No.
Instruction
Operand
0000
LD
0002
0007
STA
T0002
0001
LDA
DM0010
0008
LD
0003
0002
CON
0009
TMR
002 #00010
0003
STA
T002
0010
CON
0004
LDB
0002
0011
AND
T002
0005
LDA
DM0011
0012
OUT
0500
0006
CON
LDA / @LDA / STA @STA
KVNKA Chap 02_4cP.p65
08.3.11, 0:02 PM
142