KEYENCE Visual KV Series User Manual
Page 137

2.4 Instruction Details
1
2
3-113
Chapter 2 Instructions
Note: The double coils in different STG instruction blocks operate properly. How-
ever, when several STG instructions turn ON simultaneously, priority is given to the
one programmed last.
■ Conditional branching
When input relay 0000 (start SW) turns ON, output relay 0500 turns ON. Then, as
programmed for conditional branching, output relay 0501 turns on for 1 second
when 0001 turns ON, and 0502 turns ON for 2 seconds when 0002 turns ON. After
each operation is completed, the program returns to the conditional branch and
repeats the same steps.
Coding
1100
0001
1001
JMP
1100
DIFU
1000
STG
0002
1002
JMP
0500
T000
1000
JMP
#00010
T000
0501
1001
STG
T001
1000
JMP
#00020
T001
0502
1002
STG
1000
SET
0000
Line No.
Instruction
Operand
0000
LD
0000
0001
DIFU
1100
0002
CON
0003
AND
1100
0004
SET
1000
0005
STG
1000
0006
OUT
0500
0007
CON
0008
MPS
0009
AND
0001
0010
JMP
1001
0011
MPP
0012
AND
0002
0013
JMP
1002
0014
STG
1001
0015
OUT
0501
0016
CON
0017
TMR
000 #00010
0018
CON
0018
AND
T000
0020
JMP
1000
0021
STG
1002
0022
OUT
0502
0023
CON
0024
TMR
001 #00020
0025
CON
0026
AND
T001
0027
JMP
1000
STG / JMP
KVNKA Chap 02_4bP.p65
08.3.11, 0:00 PM
113