KEYENCE Visual KV Series User Manual
Page 360

8.2 Details
3-336
8
Chapter 8 Programming Examples
Application of STP-STE instruction
■ Process progression
When input relay 0000 turns ON, output relay 0500 automatically turns ON for 2 s,
and then 0501 turns ON for 3 s.
Ladder diagram
Coding
*
The double coil operates normally
across different STP instructions.
➮ Refer to p. 3-114.
Application of ITVL instruction
■ Pulse interval measurement
Measures the pulse interval of input relay 0000 and writes the measured data into
DM0100 (in units of 10 ms).
•
Mode No.
➞ 1 (DM0000)
•
MAX. setting value
➞ 51 (DM0001)
•
MIN. setting value
➞ 49 (DM0002)
•
Average number of measurements
➞ 10 (DM0003)
Coding
Line No.
Instruction
Operand
Line No.
Instruction
Operand
0000
LD
0000
0014
OUT
0501
0001
DIFU
1100
0015
CON
0002
CON
0016
TMR
000 #00010
0003
AND
1100
0017
CON
0004
SET
1000
0018
AND
T000
0005
STG
1000
0019
JMP
1000
0006
OUT
0500
0020
STG
1002
0007
MPS
0021
OUT
0502
0008
AND
0001
0022
CON
0009
JMP
1001
0023
TMR
001 #00020
0010
MPP
0024
CON
0011
AND
0002
0025
AND
T001
0012
JMP
1002
0026
JMP
1000
0013
STG
1001
0001
0002
0003
0004
0005
0006
0007
0008
0009
0010
0011
0012
0013
0014
0000
SET
1001
DIFU
1000 1000
STE
T001
0501
END
ENDH
SET
1002
T000
1001
STE
STP
T000
1001
T000
#00020
0500
RES
1001
T000
STP
1002
RES
1002
T001
1002
T001
#00030
Line No. Instruction
Operand
0000
LD
0000
0001
DIFU
1000
0002
CON
0003
AND
1000
0004
SET
1001
0005
STP
1001
0006
LD
T000
0007
RES
1001
0008
LDB
T000
0009
OUT
0500
0010
LD
1001
0011
TMR
000 #00020
0012
LD
T000
0013
SET
1002
0014
STE
0015
STP
1002
0016
LD
T001
0017
RES
1002
0018
LDB
T001
0019
OUT
0501
0020
LD
1002
0021
TMR
001 #00030
0022
STE
0023
END
0024
ENDH
KVNKA Chap 08.p65
08.3.11, 0:12 PM
336