Out: out oub: out bar – KEYENCE Visual KV Series User Manual

Page 89

background image

2.4 Instruction Details

1

2

3-65

Chapter 2 Instructions

Example

Coding

Description

When input relay 0000 turn ON, output relay 0500 turns ON and output relay
0501 turns OFF.

The OUT and OUB instructions are used to drive relay coils for output relays,
internal utility relays, and latch relays. These instructions are not used for input
relays, timers, counters, or data memories.

Note: Double coil
When one output relay receives input from two or more OUT or OUB instructions,
priority is given to the instruction that is entered last.

When 0001 is OFF, 0500 does not turn ON even if 0000 turns ON.

Operands

Key operation

OUT: Out

OUB: Out Bar

Outputs ON/OFF status of input to relay coil.

Outputs inverted ON/OFF status of input to
relay coil.

OUT

A

OUB

B

nnnn

nnnn

0000

0500

0501

Line No.

Instruction

Operand

0000

LD

0000

0001

OUT

0500

0002

OUB

0501

OUT

A

Operand

ENT

R-SRCH

OUB

B

Operand

ENT

R-SRCH

:

:

OUT / OUB

Visual KV

KV-300

KV-10/16

KV-24/40/80

0000 to 1915

0500 to 1915

0500 to 1915

0500 to 1915

2009

2009

2009

2009

2300 to 17915

2300 to 17915

2300 to 2915

2300 to 6915

KVNKA Chap 02_4aP.p65

08.3.11, 11:57 AM

65