beautypg.com

Kv -300 – KEYENCE Visual KV Series User Manual

Page 314

background image

6.2 High-speed Counters

KV

-300

KV-10/80

3-290

6

Chapter 6 Interrupts, High-speed Counters, Positioning Control

0000

2204

0000

SET

2204

RES

0000

2204

0000

SET

RES

KEEP

KEEP Instructions

SET/RES Instructions

Relay No.

Setting

Relay No.

Setting

2103

ON

2112

OFF

2104

OFF

2108

OFF

2105

OFF

2109

ON

2106

ON

2110

OFF

2107

OFF

2111

OFF

Special utility relay

Internal clock*

CTC0 value

CTC1 value

2100

1.0 µs

500

200

2101

10.0 µs

50

20

2102

100.0 µs

5

2

When start/stop of clock pulse is controlled by the input relay which enables/
disables the high-speed counter, response relay of up to 1 scan is generated
at start. Also, the same response relay is generated at stop, which may stop
clock pulse output while the output relay is still ON.

This controls the clock pulse so that it always starts and stops when 2205 turns
OFF.

Turn ON/OFF special utility relay 2205 as required to enable or disable output of
direct clock pulses using one of the external clocks. Use SET and RES instructions
together or only KEEP instruction to turn ON/OFF this relay.
The diagram below can be added to the sample diagram so that direct clock pulses
are output through 0501 only when 0000 is ON.

By overwriting the setting value of high-speed counter comparator CTC2 using the
LDA and STA instructions, you can change the clock pulse cycle (frequency).

Example of stopping clock pulse after reaching the specified output pulse count

The following example stops clock pulse having the pulse width of 200 µs which is
output from 0500 at cycle of 500 µs (2 kHz) after reaching the pulse count value of
10000.

Setting special utility relay, internal clock, and CTC
Settings of the special utility relays, internal clock, CTC0, and CTC1 are listed
below.

CAUTION

Coding

Line No.

Instruction

Operand

Line No.

Instruction

Operand

0000

LD

2008

0012

SET

2209

0001

MPS

0013

CON

0002

SET

2203

0014

RES

2210

0003

CON

0015

CON

0004

SET

2204

0016

RES

2211

0005

CON

0017

CON

0006

SET

2205

0018

RES

CTH1

0007

CON

0019

LD

2002

0008

RES

2207

0020

CTH

1 2201

0009

MPP

0021

CTC

2 #00050

0010

RES

2208

0022

CTC

3 #00020

0011

CON

➮ *Refer to page 3-276.

KVNKA Chap 06.p65

08.3.11, 0:10 PM

290