8.2 Details
3-335
1
8
Chapter 8 Programming Examples
Application of STG-JMP instruction
■ Enabling double coil
When start SW 0000 is pressed, output relay 0500 turns ON for 1 s, then output
relays 0500 and 0501 turn ON for 2 s, and then output relays 0500, 0501, and 0502
turn ON for 3 s. The above sequence repeats.
Ladder diagram
Coding
The double coil operates normally through different STG instructions. If
different STG instructions turn ON simultaneously, the latter programmed
instruction has the priority.
■ Conditional branching
When input relay 0000 (start SW) turns ON, output relay 0500 turns ON. Then, as
programmed for conditional branching, output 0501 turns ON for 1 s when 0001
turns ON or 0502 turns ON for 2 s when 0002 turns ON. After either one of the
processes is completed, the program returns to the conditional branching and
repeats the same steps.
Ladder diagram
0000
1001
JMP
SET
1000
1100
DIFU
1100
1000
STG
T000
#00010
T000
1002
JMP
1001
STG
T001
#00020
T001
1000
JMP
1002
STG
T002
#00030
T002
0500
0501
0502
0501
0500
0500
Turns ON 1000 when input relay 0000 turns ON.
Output relay 0500 turns ON for 1 s.
Output relays 0500 and 0501 turn ON for 2 s.
Output relays 0500, 0501 and 0502 turn ON for 3 s.
Line No.
Instruction
Operand
Line No.
Instruction
Operand
0000
LD
0000
0016
CON
0001
DIFU
1100
0017
TMR
001 #00020
0002
CON
0018
CON
0003
AND
1100
0019
AND
T001
0004
SET
1000
0020
JMP
1002
0005
STG
1000
0021
STG
1002
0006
OUT
0500
0022
OUT
0500
0007
CON
0023
CON
0008
TMR
000 #00010
0024
OUT
0501
0009
CON
0025
CON
0010
AND
T000
0026
OUT
0502
0011
JMP
1001
0027
CON
0012
STG
1001
0028
TMR
002 #00030
0013
OUT
0500
0029
CON
0014
CON
0030
AND
T002
0015
OUT
0501
0031
JMP
1000
CAUTION
0000
1001
JMP
SET
1000
1100
DIFU
1100
1000
STG
0001
1002
JMP
0002
1000
JMP
1001
STG
T000
#00010
T000
0500
0501
1000
JMP
1002
STG
T001
#00020
T001
0502
KVNKA Chap 08.p65
08.3.11, 0:12 PM
335