Page 84

2.4 Instruction Details
3-60
2
Chapter 2 Instructions
OR: Or
ORB: Or Bar
Connects N.O. contact in parallel with
previous contact.
Connects N.C. contact in parallel with
previous contact.
Example
Coding
The OR and ORB instructions are used when at least one of the conditions (here,
two sets of conditions: <0003: ON, 0004: ON>, and <0000: ON, 0001: ON, 0002:
OFF> are given) must be satisfied.
Description
•
The OR and ORB instructions are used to connect in parallel the contacts for
these instructions with contacts on the previous line. An LD or LDB instruction is
used together with the OR and ORB instructions.
•
As many contacts as desired can be connected in parallel provided they are used
in the same program.
Note: Output circuits (except for and )
cannot be included in the parallel connection.
Operands
Key operation
Example: OR T018
O R
9
ORB
6
nnnn
nnnn
0000
0003
0500
0004
0002
0001
Line No.
Instruction
Operand
0000
LD
0000
0001
OR
0000
0002
ORB
0002
0003
AND
0003
0004
OR
0004
0005
OUT
0500
(
)
SET
1
TMR
(
T
)
AND
8
O R
9
O R
9
ORB
6
Operand
ENT
R-SRCH
ENT
R-SRCH
:
:
OR / ORB
0000
0500
0501
0001
To turn ON 0500,
0000 must be ON or
0001 ON or
0002 OFF.
0003 must be ON, and
or,
0004 must be ON.
Incorrect
Visual KV
KV-300
KV-10/16
KV-24/40/80
0000 to 6915
0000 to 0009
0000 to 2915
0000 to 6915
T000 to T119
0500 to 17915
T000 to T063
T000 to T119
C000 to C119
T000 to T249
C000 to C063
C000 to C119
CTC0 to CTC3
C000 to C249
CTC0 to CTC3
CTC0 to CTC3
CTC0 to CTC3