Application of stp and ste instructions – KEYENCE Visual KV Series User Manual
Page 140

2.4 Instruction Details
3-116
2
Chapter 2 Instructions
0000
1000
T000
1001
SET
T000
1001
T000
1001
RES
0500
0501
1002
RES
STE
STE
END
ENDH
STP
1002
STP
1001
1002
SET
1000
DIFU
#00020
T000
1002
T001
T001
#00030
T001
Line No.
Instruction
Operand
0000
LD
0000
0001
DIFU
1000
0002
CON
0003
AND
1000
0004
SET
1001
0005
STP
1001
0006
LD
T000
0007
RES
1001
0008
LDB
T000
0009
OUT
0500
0010
LD
1001
0011
TMR
000 #00020
0012
LD
T000
0013
SET
1002
0014
STE
0015
STP
1002
0016
LD
T001
0017
RES
1002
0018
LDB
T001
0019
OUT
0501
0020
LD
1002
0021
TMR
001 #00030
0022
STE
0023
END
0024
ENDH
Operands
*
Note that of I/O Nos.7000 to 9915, those that are not assigned to expansion or remote I/O
unit ports can be used for internal utility relays.
Key operation
Application of STP and STE instructions
■ Process progression
When input relay 0000 turns ON, output relay 0500 turns ON for 2 seconds, then
output relay 0501 turns ON for 3 seconds automatically.
Coding
The double coils in different STP blocks operate properly.
STP / STE
FUN
FUN
LDB
4
LDB
4
ANB
5
ORL
3
Operand
(nnnn)
ENT
R-SRCH
ENT
R-SRCH
ENT
R-SRCH
ENT
R-SRCH
Visual KV
KV-300
KV-10/16
KV-24/40/80
0000 to 17915
0000 to 0009
0000 to 2915
0000 to 6915
T000 to T249
0500 to 6915
T000 to T063
T000 to T119
C000 to C249
*7000 to 9915
C000 to C063
C000 to C119
CTC0 to CTC3
T000 to T249
CTC0 to CTC3
CTC0 to CTC3
C000 to C249
CTC0 to CTC3
KVNKA Chap 02_4bP.p65
08.3.11, 0:00 PM
116