2.4 Instruction Details

3-86

2

Chapter 2 Instructions

HSP: High Speed

Shortens time constant of specified input
relay to 10 µs to increase input response.

SET

1

AND

8

FUN

HSP

nnnn

0000

HSP

0001

0001

0500

SET

0002

0501

SET

0003

0500

RES

0501

RES

Example

Coding

Timing diagram

Description

When enable input 0000 turns ON, the time constant of input 0001 (specified by
HSP) changes from 10 ms to 10 µs.

When enable input relay 0000 is ON and the scan time is 1 ms, and when the
ON time ( ) of input relays 0001 and 0002 is 5 ms, output relay 0500 turns ON
but 0502 does not.

➮ "1.4.3 Constant Scan Time Mode" (p. 3-25)

Note 1: The time constant is switched by special utility relays 2609 through 2612
with the expansion units, or by the provided switches with I/O distribution module.

Note 2: The HSP instruction is used for the input to basic units only.

Enable input

Line No.

Instruction

Operand

0000

LD

0000

0001

HSP

0001

0002

LD

0001

0003

SET

0500

0004

LD

0002

0005

SET

0501

0006

LD

0003

0007

RES

0500

0008

RES

0501

ON

ON

ON

ON

0000

0002

0001

0003

0500

0501

ON

ON

ON

ON

ON

ON

ON

OFF

ON

5 ms

5 ms

15 ms

:

HSP

KVNKA Chap 02_4aP.p65

08.3.11, 11:58 AM

86