beautypg.com

W-on: wait onw-off: wait off, W-on: wait on w-off: wait off – KEYENCE Visual KV Series User Manual

Page 120

background image

2.4 Instruction Details

3-96

2

Chapter 2 Instructions

Example

Coding

Timing chart

W-ON

When input relay 0000 is ON, output relay 0500 turns ON as soon as input operand
0001 turns ON. 0500 remains ON until 0000 turns OFF.

W-OFF

When input relay 0002 is ON, output relay 0501 turns ON as soon as input operand
0003 turns OFF. 0501 remains ON until 0002 turns OFF.

W-ON: Wait ON

W-OFF: Wait OFF

Turn ON second operand relay when first
operand relay contact turns ON.

Turns ON second operand relay when first
operand relay contact turns OFF.

Line No.

Instruction

Operand

0000

LD

0000

0001

W-ON

0001 1000

0002

LD

1000

0003

OUT

0500

0004

LD

0002

0005

W-OFF

0003 1001

0006

LD

1001

0007

OUT

0501

nnnn

OFF

mmmm

nnnn

ON

mmmm

W-ON

F

W-OFF

L i

0000

1000

0500

0001

ON

1000

0002

1001

0501

0003

OFF

1001

W-ON

W-OFF

ON

0000

0001

1000
0500

OFF

ON

OFF

ON

ON

ON

0002

0003

1001
0501

OFF

ON

OFF

ON

ON

:

:

W-ON / W-OFF

KVNKA Chap 02_4bP.p65

08.3.11, 11:59 AM

96