Mechanical installation
Important notes
4
92
EDS94SPP101 EN 7.1
4.5
Mechanical installation
4.5.1
Important notes
Note!
The devices must be installed in housings (e.g. control cabinets) to meet
applicable regulations.
4.5.2
Devices in the range 2 ... 24 A (0.37 ... 11 kW)
Proceed as follows for the installation:
1. Prepare M5 threaded holes on the mounting plate according to the mounting grid.
2. When using footprint filters: Screw installation backplane and footprint filter
together.
– Use screw and washer assemblies M5 x 20 mm or hexagon socket screws
M5 x 20 mm with washers.
– Tightening torque: 3.4 Nm (30 lb-in)
3. Screw the installation backplane or footprint filter with installation backplane onto
the mounting plate. Do not yet tighten the screws.
– Use M5 screw and washer assemblies or M5 hexagon socket screws with washers.
– The screw joint in the installation backplane may jut out no more than 7 mm.
4. Repeat steps 2 and 3 with further installation backplanes which are mounted side by
side.
5. Align all installation backplanes.
6. Screw all installation backplanes/footprint filters onto the mounting plate.
– Tightening torque: 3.4 Nm (30 lb-in).