Single-axis controllers – Lenze 9400 Manual User Manual
Page 123
Single-axis controllers
Wiring
Devices in the range 145 ... 695 A (75 ... 370 kW)
4
123
EDS94SPP101 EN 7.1
Operation with DC supply
ForoperationwithDCsupply, theinternal fansmust beconnected viathe internalterminal
FK103 to the 400/500 V AC mains voltage.
When opening the upper housing cover, you will find the pluggable terminal FK103 at the
top in the device on the switched-mode power supply card.
94SSPGG852
Interface card
Switched-mode power supply card
FK103
Fan voltage terminal
Remove the cable bridges of the terminal. Then, connect the mains voltage to
FK103.101/100.
FK103
Labelling
Description
101103 NC NC 100102
101
Fan L1
by default bridged
103
Mains phase
(internal)
NC
not assigned
NC
100
Fan L2
by default bridged
SSP94FK103
102
Mains phase
(internal)
Terminal data
Max. conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
2.5
12
0.5 ... 0.6
4.5 ... 6.2
Slot
0.6 x 3.5
With wire end
ferrule
Rated values - internal fan, AC 400 V
Gg
Type
I [A]
P [W]
8S
E94ASxE1454
0.3
120
8
E94ASxE1724
E94ASxE2024
1.2
480
9
E94ASxE2454
E94ASxE2924
E94ASxE3664
1.2
480
10
E94ASxE4604
1.2
480
E94ASxE5724
E94ASxE6354
E94ASxE6954
2.8
1120