2 operation at rated mains voltage 400 v, Operation at rated mains voltage 400 v, Power supply modules – Lenze 9400 Manual User Manual
Page 221: Input data, Output data
Power supply modules
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 400 V
6
221
EDS94SPP101 EN 7.1
6.3.2
Operation at rated mains voltage 400 V
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
LN
[V]
U
LN
[V]
f [Hz]
3/PE AC
400
320 - 0 % ... 440 + 0 %
45 - 0 % ... 65 + 0 %
Input data
Voltage
Frequency
Current [A]
Number of
phases
[V]
[Hz]
max. +45 °C c
max. +55 °C c
E94APNE0104
400
50/60
8
6
3
E94APNE0364
400
50/60
29
21.8
3
E94APNE1004
400
50/60
82
61
3
E94APNE2454
400
50/60
200
150
3
c
Temperature in the control cabinet
Voltage
Continuous input power
Type
[V]
S
L
[kVA]
E94APNE0104
400
5.5
E94APNE0364
400
20.1
E94APNE1004
400
56.7
E94APNE2454
400
138
Output data
Basis of the data
Mains
Voltage
U
DC
[V]
Voltage range
U
DC
[V]
Frequency range
f [Hz]
2/PE DC
565
455 - 0 % ... 620 + 0 %
-
Voltage
Frequency
Current [A]
Number of
phases
[V]
[Hz]
max. +45 °C c
max. +55 °C c
E94APNE0104
565
0 (DC)
10
7.5
2
E94APNE0364
565
0 (DC)
36
27
2
E94APNE1004
565
0 (DC)
100
75
2
E94APNE2454
565
0 (DC)
245
184
2
c
Temperature in the control cabinet