Accessories (overview) – Lenze 9400 Manual User Manual
Page 374
Accessories (overview)
Communication modules
DeviceNet
9
374
EDS94SPP101 EN 7.1
DIP switch
E94YCDN001D
Pos.
Switch positions
Baud rate
Node address (MAC ID)
2
1
kbps
32
16
8
4
2
1
S225
OFF
OFF
125
The station address results from the sum of the binary
valencies of the switches 1 ... 32.
z
Example: station address 44
switches 32, 8, 4 = ON (32 + 8 + 4 = 44)
z
The Lenze setting of all switches is OFF.
OFF
ON
250
ON
OFF
500
ON
ON
No function
Note!
Please observe the information about the setting of the DIP switches given in
the ”Commissioning” and ”Appendix” chapters of the E94AYCDN
communication manual (DeviceNet).
Bus cable length
Depending on the baud rate and the cable type used (thick cable/thin cable), the following
bus cable lengths are possible:
Baud rate [kbps]
Bus cable lengths [m]
Thick cable
Thin cable
125
500
100
250
250
500
100
If both thick and thin cable types are used, the maximum cable lengths can be defined
according to the baud rates as follows:
Baud rate [kbps]
Max. bus cable length
125
500 m = L
thick
+ 5 L
thin
250
250 m = L
thick
+ 2.5 L
thin
500
100 m = L
thick
+ L
thin
L
thick
: thick cable length
L
thin
: thin cable length
Note!
Select a baud rate in dependency of the data volume, cycle time and number
of nodes just high enough to suit your application.