Accessories (overview), Stop – Lenze 9400 Manual User Manual
Page 395
Accessories (overview)
Function modules
Digital frequency
9
395
EDS94SPP101 EN 7.1
Assignment of the Sub-D plug connector
Stop!
The output voltages on X9/4 and on X10/4 may not be interconnected. This
applies to both the wiring of several modules and to the wiring of one module
(e. g. for purposes of simulation).
Use system cables not connecting pin 4 for this applications only.
Tip!
We recommend the use of Lenze system cables. For this purpose, please read
the documentation for the basic device.
X9
Pin
Designation
Explanation
1
6
5
9
1
B
TTL input signal by encoder or encoder simulation
2
A
3
A
4
+5 V
Regulated voltage supply for encoder
(pin 8 = sense must be used, max. control range 5 ... 9 V)
5
GND
-
6
Z
TTL input signal by encoder or encoder simulation
7
Z
8
The function of this cable has to be set in the basic device:
z
S
z
Lc
z
E
z
Sense (sensor lead for voltage regulation, Lenze setting)
z
Lamp control
z
Enable
SUBD09010
9
B
TTL input signal by encoder or encoder simulation
X10
Pin
Designation
Explanation
1
6
5
9
1
B
TTL output signal from encoder or encoder simulation
2
A
3
A
4
+5 V
V
CC
±6 %
5
GND
-
6
Z
TTL output signal from encoder or encoder simulation
7
Z
8
Enable
Digital output signal
SUBD09010
9
B
TTL output signal from encoder or encoder simulation