Single-axis controllers – Lenze 9400 Manual User Manual
Page 91
Single-axis controllers
Device description
Devices in the range 145 ... 695 A (75 ... 370 kW)
4
91
EDS94SPP101 EN 7.1
Pos.
Description
MXI1
Module receptacle for extension 1, e.g. communication
MXI2
Module receptacle for extension 2, e.g. communication
MMI
Module receptacle for memory modules
MSI
Module receptacle for safety equipment
X1
System bus (CAN), under the cover
X2
24-V supply / Statebus
X3
Analog inputs / analog outputs
X4
Digital outputs
X5
Digital inputs
X6
Diagnostics (with diagnostic adapter or keypad)
X7
Resolver
X8
Encoder
Lower cover
Retractable nameplate
Upper cover
EMC wire clamp
X100
Mains / DC-bus voltage
X105
Motor / external brake resistor
X106
Motor temperature monitoring (position depends on the device size)
X107
Control of motor holding brake
EMC shield clamp
Holes for transport and assembly guides
Shield connection/strain relief (device sizes: 8S, 8 and 9)
Barrier between mains input and other power terminals (device sizes: 8S, 8 and 9)
Switch for operation in IT systems
The LED display enables fast indication of several operating states.
LED
Labelling
Colour
Description
CAN-RUN
green
CAN bus ok
CAN-ERR
red
CAN bus error
DRIVE READY
green
Standard device is ready for operation
DRIVE ERROR
red
Error in the standard device or application-induced
24 V
green
24 V supply voltage ok
SSP94LED01
USER
yellow
Message parameterised by the application
Pos.
Symbol
Description
Long discharge time: All power terminals carry hazardous voltages for at
least 20 minutes after mains disconnection!
High discharge current: Fixed installation and PE connection to EN 61800-5-1
required!
Electrostatic sensitive devices: Before working on the device, the personnel
must remove any electrostatic charges using suitable measures!