Single-axis controllers – Lenze 9400 Manual User Manual
Page 62

Single-axis controllers
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 500 V
4
62
EDS94SPP101 EN 7.1
Output currents [A] at switching frequency
2 kHz
4 kHz
8 kHz
16 kHz
4)
Type
I
aN2
I
aM2
I
aN4
I
aM4
I
aN8
I
aM8
I
aN16
E94ASxE0024
1.9
3)
6.0
1.9
3)
6.0
1.3
4.2
1.0
E94ASxE0034
3.1
3)
10.0
3.1
3)
10.0
2.2
7.0
1.6
E94ASxE0044
5.0
3)
16.0
5.0
3)
16.0
3.5
11.2
2.6
E94ASxE0074
8.8
3)
21.0
8.8
3)
21.0
6.1
14.7
4.6
E94ASxE0134
16.3
3)
39.0
16.3
3)
39.0
11.4
27.3
8.5
E94ASxE0174
20.6
3)
49.5
20.6
3)
49.5
14.4
34.7
10.8
E94ASxE0244
29.4
3)
58.8
29.4
3)
58.8
20.6
41.1
15.4
4)
E94ASxE0324
38.4
76.8
33.6
67.2
28.0
64.0
16.8
E94ASxE0474
47.0
94.0
41.1
82.2
35.8
71.6
21.5
E94ASxE0594
59.0
118
51.6
103
35.9
71.8
21.5
E94ASxE0864
86.0
172
75.3
150
63.9
127
38.3
E94ASxE1044
104
208
91.0
182
68.3
136
40.9
E94ASxE1454
145
261
145
261
89
161
-
E94ASxE1724
172
310
172
310
105
189
-
E94ASxE2024
202
364
202
364
115
206
-
E94ASxE2454
245
441
209
376
140
252
-
E94ASxE2924
292
526
250
450
167
301
-
E94ASxE3664
366
659
313
563
210
378
-
E94ASxE4604
460
828
368
662
228
410
-
E94ASxE5724
572
1030
458
824
250
450
-
E94ASxE6354
635
1143
508
914
278
500
-
E94ASxE6954
695
1251
556
1001
305
549
-
I
aN2
Rated value of permanent output current at a frequency of ≥ 0 Hz
I
aM2
Maximum output current (overload current) at frequency ≥ 0 Hz
E94ASxE0024 ... E94ASxE1044:
z
Periodic load change of 0.5 s with I
aM2
and recovery time of 4.5 s with
75 % I
aN2
E94ASxE1454 ... E94ASxE6954:
z
Periodic load change of 10 s with I
aM2
and recovery time of 50 s with
75 % I
aN2
I
aN4
, I
aN8,
I
aN16
Rated value of continuous output current at a frequency of ≥ 5 Hz
(reduce to 0.66 * I
aNx
for 0 ... 5 Hz)
I
aM4
, I
aM8
Maximum output current (overload current) at frequency ≥ 5 Hz
(reduce to 0.66 * I
aMx
for 0 ... 5 Hz)
z
Can be achieved using the setting ”x kHz fixed” in C00018
E94ASxE0024 ... E94ASxE1044:
z
Periodic load change of 0.5 s with I
aMx
and recovery time of 4.5 s with
75 % I
aNx
E94ASxE1454 ... E94ASxE6954:
z
Periodic load change of 10 s with I
aM2
and recovery time of 50 s with
75 % I
aN2
bold
Nominal value I
aN
3)
Operation with permanent currents > I
aN8
requires an external mains choke.
4)
Temperature inside the control cabinet = +35 ... +55 °C: 2.5 %/K current
derating