5 design of the cables, 6 how to connect the shield, Design of the cables – Lenze 9400 Manual User Manual
Page 297: How to connect the shield, Regenerative power supply modules
Regenerative power supply modules
Wiring
Design of the cables
7
297
EDS94SPP101-7.1
7.6.5
Design of the cables
ƒ
The cables used must comply with the approvals required for the location (e.g. UL).
ƒ
It is imperative to comply with the regulations concerning minimum cross-sections
of PE conductors. The cross-section of the PE conductor must be at least as large as
the cross-section of the power connections.
ƒ
The effectiveness of a shielded cable is reached by:
– Providing a good shield connection through large-surface shield contact.
– Using only braided shields with low shield resistance made of tin-plated or
nickel-plated copper braid.
– Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
– Keeping unshielded cable ends as short as possible.
Use system cables or shielded cables for these connections:
ƒ
External brake resistor ( Mounting Instructions of the brake resistor)
ƒ
Analog signals (inputs and outputs)
ƒ
CAN system bus
ƒ
Resolver
ƒ
System connection for synchronisation
The following connections need not be shielded:
ƒ
Mains
ƒ
DC bus
ƒ
24 V supply
ƒ
Digital signals (inputs and outputs)
7.6.6
How to connect the shield