7 cable protection, 8 filters, Cable protection – Lenze 9400 Manual User Manual
Page 331: Filters, Dc-bus operation
DC-bus operation
Basic dimensioning
Cable protection
8
331
EDS94SPP101 EN 7.1
8.5.7
Cable protection
In case of interferences, the cables have to be adequately protected (8.4.4).
Please consider the following when dimensioning the DC bus for a plant or machine:
ƒ
Mains fuses can be used to protect the DC cables if the wiring is designed for 122 %
of the rated fuse current. Otherwise, the cable protection for the DC cables must be
specially determined.
ƒ
Select the fuses for the currents resulting from power P
DC100%
. Please observe the
standards and regulations applicable for the particular location and application.
ƒ
Fuse the DC-supply modules according to the Technical data on the AC mains side.
ƒ
The DC outputs of the supply modules need not be fused if all connected controllers
are fused in accordance with the specifications.
ƒ
”Multi Drive” controllers are default equipped with a fuse in the installation
backplane. The fuse is only effective if the DC busbar is used. In this case, a single
pole fusing against short-circuit is sufficient.
ƒ
”Single Drive” controllers can be retrofit with a fuse in the mounting backplane. The
fuse will only be effective if the DC busbar is used. In this case, a single-pole fusing
against short-circuit is sufficient.
For retrofitting, use the E94AZJA0xx busbar mounting set.
ƒ
If the DC bus is wired via the terminals +UG/-UG, always select a 2-pole cable
protection.
8.5.8
Filters
The following filters can be used for the DC-supply modules.
Mains filter
DC power supply module
Type
Device size
Type
Device size
E94AZMP0084
2
E94APNE0104
1
E94AZMP0294
3
E94APNE0364
3
E94AZMP0824
4
E94APNE1004
4
E94AZMP2004
5
E94APNE2454
5
The mains filters are designed for the following conditions:
ƒ
10 interconnected devices,
ƒ
each with a 50 m motor cable,
ƒ
EMC category C2.