7 application examples, Dc-bus operation – Lenze 9400 Manual User Manual
Page 336
DC-bus operation
Application examples
Example 1
8
336
EDS94SPP101 EN 7.1
8.7
Application examples
8.7.1
Example 1 - supply module with multi-axis controllers
Assumptions:
ƒ
400 V, 3 AC/PE
ƒ
7 axes in 2 power categories
ƒ
no particular dynamic performance requirements
The following motors (Mx) are selected:
Motor type
Rated power
Efficiency
Rated current
Index
[kW]
[A]
M1 ... M5
MCS14H15
2.5
0.92
6.6
M6 ... M7
MCS09F38
1.2
0.90
2.5
For the above motor data, the following controllers (Gx) are selected:
Controller
Rated power
Typical motor
power
Power loss P
l
Rated current
Index
[kW]
[kW]
[kW]
[A]
G1 ... G5
E94AMxE0074
4.8
3.0
0.19
7.0
G6 ... G7
E94AMxE0034
1.7
0.75
0.12
2.5
The power required by the drive system is determined with the below formula ( 8.5.5):
P
DCtotal
= 5 * (2.5 kW / 0.92 + 0.19 kW) + 2 * (1.2 kW / 0.90 + 0.12 kW)
P
DCtotal
= 17.4 kW
The calculated power requirement is used to select the supply module:
Supply module (+ mains filter)
Rated power (P
DC100%
)
Index
[kW]
V1
E94APNE0364
+ E94AZMP0294
17.5
Note: Only the supply module with mains filter reaches the required power.
Checking the power efficiency:
With 17.5 kW > 17.4 kW, P
DC100%
> P
DCtotal
.
Select cables and fuses in accordance with the Technical data.
L2
L1
L3
M
M
M
3
AC
M
...
V1
G 1
G x
Fig. 8-4
Basic circuit diagram