Accessories (overview) – Lenze 9400 Manual User Manual
Page 417
Accessories (overview)
Safety modules
SM301
9
417
EDS94SPP101 EN 7.1
Connection data
Note!
Provide for a sufficient strain relief, so that the terminals are not pulled from
the plug connectors, in particular when you use rigid cables.
Cable cross-sections and tightening torques
Type
[mm
2
]
[Nm]
AWG
[lb-in]
Wire end ferrule,
insulated
0.25 ... 0.75
Spring terminal
24 ... 18
Spring terminal
Rigid
0.14 ... 1.5
26 ... 16
Stripping length or contact length: 9 mm
X82.1
Labelling
Description
This part of the terminal strip is not assigned.
GO
GND SD-Out1
O1B
Safe monitor SD-Out1, channel B
O1A
Safe monitor SD-Out1, channel A
This part of the terminal strip is not assigned.
X82.2
Labelling
Description
-
GND external supply
+
+24 V external supply via a safely separated power supply unit (SELV/PELV)
GIR
This part of the terminal strip is reserved.
RI1
GO
GND 24O
24O
+24 V external supply for the safe monitor SD-Out1 (SELV/PELV)
AIE
Error acknowledgement input (”Acknowledge In Error”)
CLA
Clock output for passive sensors, channel A (Clock A)
CLB
Clock output for passive sensors, channel B (Clock B)
X82.3
Labelling
Description
GCL
GND clock output
GI2
GND SD-In2
I2B
Sensor input SD-In2, channel B
I2A
Sensor input SD-In2, channel A
GCL
GND clock output
GI1
GND SD-In1
I1B
Sensor input SD-In1, channel B
I1A
Sensor input SD-In1, channel A
AIS
Restart acknowledgement input (”Acknowledge In Stop”, 1-channel,
bridged to X82.4/AIS)