6 wiring, 1 important notes, Important notes – Lenze 9400 Manual User Manual
Page 242: Power supply modules
Power supply modules
Wiring
Important notes
6
242
EDS94SPP101 EN 7.1
6.6
Wiring
6.6.1
Important notes
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Death or severe injuries when touching the power terminals.
Protective measures:
ƒ
Switch off the power supply and wait for at least three minutes before
working on the power terminals.
ƒ
Make sure that all power terminals are deenergised.
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Death or severe injuries when the device is touched in the event of a fault.
Protective measures:
ƒ
Implement the actions required in the EN 61800-5-1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter
≥
10 mm
2
or PE conductor must be connected twice)
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ
Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ
Observe the maximally permissible mains voltage.
ƒ
Fuse the device correctly on the supply side against mains fluctuations and
voltage peaks.