1 operation at rated mains voltage 230 v, Operation at rated mains voltage 230 v, Power supply modules – Lenze 9400 Manual User Manual
Page 219: Input data, Output data
Power supply modules
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 230 V
6
219
EDS94SPP101 EN 7.1
6.3.1
Operation at rated mains voltage 230 V
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
LN
[V]
U
LN
[V]
f [Hz]
3/PE AC
230
180 - 0 % ... 264 + 0 %
45 - 0 % ... 65 + 0 %
Input data
Voltage
Frequency
Current [A]
Number of
phases
[V]
[Hz]
max. +45 °C c
max. +55 °C c
E94APNE0104
230
50/60
8
6
3
E94APNE0364
230
50/60
29
21.8
3
E94APNE1004
230
50/60
82
61
3
E94APNE2454
230
50/60
200
150
3
c
Temperature in the control cabinet
Voltage
Continuous input power
Type
[V]
S
L
[kVA]
E94APNE0104
230
3.2
E94APNE0364
230
11.5
E94APNE1004
230
32.6
E94APNE2454
230
79.6
Output data
Basis of the data
Mains
Voltage
U
DC
[V]
Voltage range
U
DC
[V]
Frequency range
f [Hz]
2/PE DC
325
260 - 0 % ... 370 + 0 %
-
Voltage
Frequency
Current [A]
Number of
phases
[V]
[Hz]
max. +45 °C c
max. +55 °C c
E94APNE0104
325
0 (DC)
10
7.5
2
E94APNE0364
325
0 (DC)
36
27
2
E94APNE1004
325
0 (DC)
100
75
2
E94APNE2454
325
0 (DC)
245
184
2
c
Temperature in the control cabinet