Single-axis controllers – Lenze 9400 Manual User Manual
Page 67
Single-axis controllers
Rated data (devices for 400/500V mains)
Fuses and cable cross-sections
4
67
EDS94SPP101 EN 7.1
Operation without external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
c
d
L1, L2, L3 - Laying system
e
L1, L2, L3
B2
C
F
[A]
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[A]
[AWG]
[mA]
E94ASxE0024
C10
-
1,5
1,5
-
10
18
≥
300
E94ASxE0034
C10
-
1.5
1.5
-
10
18
≥
300
E94ASxE0044
C10
-
1.5
1.5
-
10
18
≥
300
E94ASxE0074
C16
-
2.5
2.5
-
15
16
≥
300
E94ASxE0134
C20
-
2.5
2.5
-
20
12
≥
300
E94ASxE0174
C25
-
4
4
-
25
10
≥
300
E94ASxE0244
C40
-
10
6
-
40
8
≥
300
E94ASxE0324
4)
-
40
10
6
-
40
8
≥
300
E94ASxE0474
4)
-
63
16
10
-
60
4
≥
300
E94ASxE0594
4)
-
80
25
25
-
80
2
≥
300
E94ASxE0864
4)
-
100
50
35
-
100
1
≥
300
E94ASxE1044
4)
-
125
70
50
-
125
0
≥
300
E94ASxE1454
4)
-
200
-
-
70
250
000
≥
300
E94ASxE1724
4)
-
250
-
-
95
300
350 mcm
≥
300
E94ASxE2024
4)
-
315
-
-
150
350
500 mcm
≥
300
E94ASxE2454
4)
-
350
-
-
150
2 x 200
0000
≥
300
E94ASxE2924
4)
-
400
-
-
185
2 x 250
2 x 250 mcm
≥
300
E94ASxE3664
4)
-
500
-
-
240
2 x 300
2 x 350 mcm
≥
300
E94ASxE4604
4)
-
2 x 350
-
-
150
2 x 350
500 mcm
≥
300
E94ASxE5724
4)
-
2 x 400
-
-
185
2 x 400
600 mcm
≥
300
E94ASxE6354
4)
-
2 x 450
-
-
240
2 x 400
600 mcm
≥
300
E94ASxE6954
4)
-
2 x 500
-
-
240
2 x 400
600 mcm
≥
300
1)
The details are recommendations. Other designs/laying systems are possible (e.g. according to VDE 0298-4). The
cable cross-sections apply under the following conditions: the use of PVC-insulated copper cables, conductor
temperature < 70°C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
UL approved cables only, fuses and fuse holders must be used.
UL fuse: voltage 500 ... 600 V
3)
Universal-current sensitive earth-leakage circuit breaker
If several devices or cable lengths > 50 m are used, the circuit breaker may respond, depending on the cable type and
switching frequency.
4)
Device with integrated mains choke
c
Circuit breaker
d
Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
e
Fuse
Observe national and regional regulations