Accessories (overview), Dc input module components, Standards – Lenze 9400 Manual User Manual
Page 482: Operating conditions
Accessories (overview)
Components for operation in the DC-bus connection
DC-feeding point
9
482
EDS94SPP101 EN 7.1
DC input module components
Pos.
Description
Nameplate
X109
+UG busbar input
X110
-UG busbar input
X119
+UG cable input
X120
-UG cable input
X129
+UG cable output
X130
-UG cable output
Standards
Conformity and approval
Conformity
CE
2006/95/EC
Low-voltage directive
Approval
UL
UL 508C
Power Conversion Equipment, File No. 132659
GOST-R
51321.1-2000
51321.3-99
No. POCC DE.AN30.B08815
Protection
Enclosure
EN 60529
IP 20
NEMA 250
Protection against accidental contact acc. to type 1
Insulation resistance
EN 61800-5-1
Overvoltage category III
Reduction from 2000 m: Overvoltage category II
Operating conditions
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1
1K3 (-25 ... +60 °C)
Transport
IEC/EN 60721-3-2
2K3 (-25 ... +70 °C)
Operation
IEC/EN 60721-3-3
3K3 (-10 ... +55 °C)
Current derating at +45 ... +55 °C:
Device size 1 ... 7: 2.5 %/°C
Device size 8S ... 10: 1 %/°C
Site altitude
0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m
Pollution
EN 61800-5-1
Degree of pollution 2
Vibration resistance
(9.81 m/s
2
= 1 g)
Transport
IEC/EN 60721-3-2
2M2
EN 61800-2
2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd
5 ... 13.2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
IEC/EN 60068-2-6
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g