5 mechanical installation, 1 important notes, Important notes – Lenze 9400 Manual User Manual
Page 285: Regenerative power supply modules
Regenerative power supply modules
Mechanical installation
Important notes
7
285
EDS94SPP101-7.1
7.5
Mechanical installation
7.5.1
Important notes
Note!
The devices must be installed in housings (e.g. control cabinets) to meet
applicable regulations.
Stop!
Heavy device weight
The device is very heavy and must be lifted for the mounting.
Possible consequences:
ƒ
Injury to persons, particularly backache when lifting and holding the device,
respectively
ƒ
Injury to persons and damage to material assets due to the device falling
down
Protective measures:
ƒ
The device must only be carried with a load bearing system such as an
indoor crane permitted for the device weight
ƒ
Before the transport, the hoist, the load bearing system and lifting
accessories must be checked for sufficient payload and faultless status
ƒ
Do not remove the hoist and the lifting accessories until the device lies safe
on a stable surface or is finally mounted.
ƒ
The mounting location must always fulfill the operating conditions specified in the
Technical data. ( 263). If necessary, take additional measures.
ƒ
The mounting plate of the control cabinet must be:
– electrically conductive
– free of lacquer
ƒ
The mechanical connections must always be ensured.
ƒ
The described EMC properties are provided if the following conditions are complied
with:
– The devices are mounted according to the arrangement concept described.
– The prepared cables are used and remain unchanged.