Multi-axis controllers, 2 operation on 400 v, Mains – Lenze 9400 Manual User Manual
Page 166
Multi-axis controllers
Rated data
Devices for 400/500V-mains
5
166
EDS94SPP101 EN 7.1
5.3.2.2
Operation on 400 V
AC
mains
Basis of the data
Mains
Voltage
U
DC
[V]
Voltage range
U
DC
[V]
Frequency range
f [Hz]
2/PE DC
565
455 - 0 % ... 620 + 0 %
-
Input current at I
aN8
Output power
Motor power
(typical)
(without external mains
choke)
8 kHz, U, V, W
8 kHz, 4 pol. ASM
Type
I
DC
[A]
S
aN8
[kVA]
P
aN
[kW]
P
aN
[hp]
E94AMxE0024
2.6
1.0
0.37
0.5
E94AMxE0034
4.3
1.7
0.75
1
E94AMxE0044
6.7
2.8
1.5
2
E94AMxE0074
12.1
4.8
3
4
E94AMxE0094
15.4
6.5
4
5
E94AMxE0134
20.6
9.0
5.5
7.5
E94AMxE0174
25.7
11.4
7.5
11
E94AMxE0244
35.5
16.3
11
15
Output currents [A] at switching frequency
2 kHz
4 kHz
8 kHz
16 kHz
4)
Type
I
aN2
I
aM2
I
aN4
I
aM4
I
aN8
I
aM8
I
aN16
E94AMxE0024
1.9
6.0
1.9
6.0
1.5
4.8
1.1
E94AMxE0034
3.1
10.0
3.1
10.0
2.5
8.0
1.9
E94AMxE0044
5.0
16.0
5.0
16.0
4.0
12.8
3.0
E94AMxE0074
8.8
21.0
8.8
21.0
7.0
16.8
5.3
E94AMxE0094
11.7
28.0
11.7
28.0
9.3
22.4
7.0
E94AMxE0134
16.3
39.0
16.3
39.0
13.0
31.2
9.8
E94AMxE0174
20.6
49.5
20.6
49.5
16.5
39.6
12.4
E94AMxE0244
29.4
70.5
29.4
70.5
23.5
56.4
17.6
I
aN2
Rated value of permanent output current at a frequency of ≥ 0 Hz
I
aM2
Maximum output current (overload current) at frequency ≥ 0 Hz
z
Periodic load change of 0.5 s with I
aM2
and recovery time of 4.5 s with
75 % I
aN2
I
aN4
, I
aN8,
I
aN16
Rated value of continuous output current at a frequency of ≥ 5 Hz
(reduce to 0.66 * I
aNx
for 0 ... 5 Hz)
I
aM4
, I
aM8
Maximum output current (overload current) at frequency ≥ 5 Hz
(reduce to 0.66 * I
aMx
for 0 ... 5 Hz)
z
Periodic load change of 0.5 s with I
aMx
and recovery time of 4.5 s with
75 % I
aNx
z
Can be achieved using the setting ”x kHz fixed” in C00018
bold
Nominal value I
aN