Single-axis controllers, General data and operating conditions, V/f control mode – Lenze 9400 Manual User Manual
Page 43
Single-axis controllers
General data and operating conditions
4
43
EDS94SPP101 EN 7.1
Longer motor cables can be achieved when line filters are used in combination with
sinusoidal filters. Further conditions to be observed:
ƒ
V/f control mode
ƒ
Switching frequency is permanently set (C00018)
Motor cable lengths when sinusoidal filters and line filters are used
Compliance with the EMC protection requirement C2
Type
RFI filter
Mains filter
Sinusoidal filter
shielded
unshielded
Switching
frequency
E94ASxE0024
-
E94AZMS0034
EZS3-004A200
100 m
300 m
4 kHz
or
8 kHz
E94ASxE0034
E94ASxE0044
-
E94AZMS0094
EZS3-010A200
E94ASxE0074
E94ASxE0134
-
E94AZMS0184
EZS3-024A200
E94ASxE0174
E94ASxE0244
-
E94AZMS0314
EZS3-037A200
E94ASxE0324
E94AZRS0544
-
EZS3-048A200
150 m
300 m
4 kHz
or
8 kHz
E94ASxE0474
EZS3-061A200
E94ASxE0594
EZS3-072A200
E94ASxE0864
E94AZRS0954
-
EZS3-115A200
150 m
300 m
2 kHz
or
4 kHz
E94ASxE1044
EZS3-150A200
E94ASxE1454
-
-
EZS3-180A200
150 m
- m
2 kHz
or
4 kHz
E94ASxE1724
-
-
EZS3-250A200
E94ASxE2024
-
-
EZS3-250A200
E94ASxE2454
-
-
EZS3-350A200
E94ASxE2924
-
-
EZS3-350A200
E94ASxE3664
-
-
EZS3-480A200
E94ASxE4604
-
-
EZS3-350A200
(2 in parallel)
E94ASxE5724
-
-
EZS3-480A200
(2 in parallel)
E94ASxE6354
-
-
EZS3-480A200
(2 in parallel)
E94ASxE6954
-
-
EZS3-350A200
(3 in parallel)
Tab. 4-3
EMC limit value class for conducted noise emission in TN/TT systems:
C2 to EN 61800-3 corresponds to class A to EN 55011