General data and operating conditions
General data
Conformity and approval
Conformity
CE
2006/95/EC
Low-voltage directive
Approval
UL
UL 508C
Power Conversion Equipment, File No. 132659
GOST-R
51321.1-2000
51321.3-99
No. POCC DE.AN30.B08815
Protection of persons and devices
Enclosure
EN 60529
IP 20
Not in the wire range of
the terminals on the
motor side
NEMA 250
Protection against contact in
accordance with type 1
Insulation resistance
EN 61800-5-1
Overvoltage category III
Reduction from 2000 m amsl onwards: Overvoltage category
II
Insulation of control
circuits
EN 61800-5-1
Safe mains isolation by double/reinforced insulation for
mains with neutral earthing with a rated voltage for the
external conductor/star point up to 300 V.
Short-circuit strength
EN 61800-5-1
Motor connection: with restrictions, error acknowledgement
required
Control connections: without restrictions
Motor - protective
measures against
z
Short circuit
z
Earth fault
z
Overvoltage
z
Motor stalling
z
Motor overtemperature
(PTC or thermal contact, I
2
t monitoring)
Discharge current
EN 61800-5-1
> 3.5 mA AC, > 10 mA DC
Observe regulations and
safety instructions!
Cyclic mains switching
Cyclic mains switching of 5 times in 5 minutes is permissible
without restrictions.
Design
Housing
Carrier housing
Device sizes
1, 2 and 3
Glass-fiber reinforced plastic
Carrier housing
Device sizes
as of 6
Metal
Dimensions
see ”Mechanical installation”
Weight
see ”Mechanical installation”
Mounting conditions
Mounting place
In the control cabinet
Mounting position
Vertical
Mounting clearances
Above/below
≥
80 mm / ≥ 120 mm
Observe the device-related
notes on mounting.
To the sides
Side-by-side mounting without
any clearance