3 operation at a rated mains voltage of 500 v, Operation at a rated mains voltage of 500 v, Power supply modules – Lenze 9400 Manual User Manual
Page 223: Input data, Output data
Power supply modules
Rated data (devices for 400/500V mains)
Operation at a rated mains voltage of 500 V
6
223
EDS94SPP101 EN 7.1
6.3.3
Operation at a rated mains voltage of 500 V
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
LN
[V]
U
LN
[V]
f [Hz]
3/PE AC
500
400 - 0 % ... 550 + 0 %
45 - 0 % ... 65 + 0 %
Input data
Voltage
Frequency
Current [A]
Number of
phases
[V]
[Hz]
max. +45 °C c
max. +55 °C c
E94APNE0104
500
50/60
8
6
3
E94APNE0364
500
50/60
29
21.8
3
E94APNE1004
500
50/60
82
61
3
E94APNE2454
500
50/60
200
150
3
c
Temperature in the control cabinet
Voltage
Continuous input power
Type
[V]
S
L
[kVA]
E94APNE0104
500
6.9
E94APNE0364
500
25.1
E94APNE1004
500
70.9
E94APNE2454
500
173
Output data
Basis of the data
Mains
Voltage
U
DC
[V]
Voltage range
U
DC
[V]
Frequency range
f [Hz]
2/PE DC
705
565 - 0 % ... 775 + 0 %
-
Voltage
Frequency
Current [A]
Number of
phases
[V]
[Hz]
max. +45 °C c
max. +55 °C c
E94APNE0104
705
0 (DC)
10
7.5
2
E94APNE0364
705
0 (DC)
36
27
2
E94APNE1004
705
0 (DC)
100
75
2
E94APNE2454
705
0 (DC)
245
184
2
c
Temperature in the control cabinet