Accessories (overview)
Communication modules
Ethernet interface
9
363
EDS94SPP101 EN 7.1
Connections
Pos.
Description
X245
Connection for the external supply of the communication module
Design: Plug connector with spring connection, 2-pole
X246
EtherCAT input (IN)
Design: RJ45 socket according to IEC 60603-7
X247
EtherCAT output (OUT)
Design: RJ45 socket according to IEC 60603-7
Displays
LED
Description
Pos.
Colour
Condition
MS
green
blinking
The communication module is supplied with voltage but has no
connection to the standard device (standard device is either switched off,
in the initialisation phase, or not available).
on
The communication module is being supplied with voltage and is
connected to the standard device.
ME
red
on
A communication module error has occurred.
BS
green
off
The communication module is in the ”Init” status (initialisation phase).
blinking
(2.5 Hz)
The communication module is in the ”Pre-Operational” status.
blinking
(1.0 Hz)
The communication module is in the ”Safe-Operational” status.
flickering
The communication module is booting and has not yet reached the ”Init”
status (initialisation phase).
on
The communication module is in the ”Operational” status.
BE
red
blinking
Bus error/trouble is active (e.g. the Ethernet cable is unplugged). The LED
is blinking in parallel to the BS LED.
DE
red
on
The communication module is not accepted by the standard device or
the standard device is not active. (See notes provided in the
documentation for the standard device.)
Signalling at connection X246/X247:
-
Red
On / blinking The EtherCAT connection is disrupted or not available.
-
Green
On / blinking
z
The EtherCAT connection is available.
z
The data communication of the EtherCAT connection is active.